Deye GE-FH60-FL60
A 61.44 kWh high-voltage battery cabinet with 100% usable depth of discharge, layered fire protection and grouping up to 500 kW / 3,600 kWh for commercial sites.
Technical Specifications
| Parameter | DEYE-GE-FH60-FL60 |
|---|---|
| Battery Data | |
| Energy | 5.12 kWh |
| Usable Energy | 61.44 kWh |
| Module Energy | 5.12 kWh |
| System Energy | 61.44 kWh |
| Max. Capacity | 3600 kWh |
| Nominal Voltage | 51.2 V |
| Module Nominal Voltage | 51.2 V |
| System Nominal Voltage | 614.4 V |
| Operating Voltage | 480-700 V |
| Rated Capacity | 100 Ah |
| Module Capacity | 100 Ah |
| Cell Chemistry | LiFePO4 |
| Cycle Life | >6000 |
| End-of-Life Capacity | 70% |
| Recommended Depth of Discharge | 100% |
| Rated DC Power | 61.44 kW |
| Max. Charge Current | 125 A |
| Max. Discharge Current | 125 A |
| Max. Charge/Discharge Current | 125 A |
| Nominal Charge/Discharge Current | 100 A |
| Recommended Charge/Discharge Current | 50 A |
| Peak Discharge Current | 125 A |
| Modules in Series | 12 |
| Min. Battery Module Quantity | 12 |
| Parallel Units | 6 |
| Protection Features | Combustible Gas Detection, Smoke Detection, Temperature Detection, Active Exhaust, Fire Alarm |
| Protection Level | I |
| Warranty (Years) | 10 |
| Mechanical & Interface | |
| Communication Ports | CAN2.0, RS485 |
| Dimensions | 783 x 2235 x 1059 mm |
| Additional Notes | Max 10 AC parallel groups (up to 500kW/3600kWh); Black Start support |
| Status Indicator | Yellow: Battery High Voltage Power On; Red: Battery System Alarm |
| Weight | 1070 kg |
| Environment & Protection | |
| Altitude | <2000 m |
| Charge Temperature | 0-55 °C |
| Discharge Temperature | -20 to 55 °C |
| Fire Suppression | Aerosol |
| Operating Humidity | 5-85% |
| Installation Location | Floor-Mounted |
| Enclosure IP Rating | IP55 |
| Storage Temperature | 0-35 °C |
| Working Temperature | -30 to 60 (>45 derating) °C |
Figures are measured at the test conditions the manufacturer’s datasheet states. A dash means the manufacturer publishes no figure for that model.
Availability & grid compliance in Oman
| Market | Oman |
| Grid authority / regulator | Authority for Electricity Regulation Oman |
| Quotation currency | OMR |
| Support hours timezone | Asia/Muscat |
| Delivery & installation coverage | Muscat, Salalah, Sohar |
Figures on this page are the manufacturer's own, measured at the test conditions the datasheet states — they do not change by country. What changes is the approval that has to be met before the unit is energised: in Oman that is Authority for Electricity Regulation Oman. Confirm the grid code, import requirements and any local certification with them, or with us, before you order.
Key Features & Technical Highlights
- Fully usable 61.44 kWh: Usable energy equals the full 61.44 kWh rating, at a recommended 100% depth of discharge.
- Layered fire protection: Aerosol suppression backed by combustible-gas, smoke and temperature detection, active exhaust and a fire alarm.
- 614.4 V high-voltage stack: Twelve 5.12 kWh modules in series feed inverters across a 480-700 V window at 61.44 kW.
- Runs from -30 to 60 °C: The working range spans -30 to 60 degrees C, with derating above 45 degrees.
- Grows to 500 kW: Six units parallel directly and up to 10 AC groups reach 500 kW and 3,600 kWh, with Black Start support.
- Certified and warranted: Certification covers UN38.3, CE, CEC, IEC62040 and CB, alongside a stated 10-year warranty.
Frequently Asked Questions
What voltage class do the GE-FH60 & GE-FL60 belong to?
The cabinet runs at a nominal 614.4 V with an operating window of 480-700 V, so it partners high-voltage inverters and never a 48 V hybrid unit.
How much of the 61.44 kWh is actually usable?
All of it - the usable energy is stated as 61.44 kWh with a recommended depth of discharge of 100%.
How does the GE-FH60 & GE-FL60 handle fire risk?
It combines aerosol fire suppression with combustible-gas detection, smoke detection, temperature detection, active exhaust and a fire alarm.
How far can a GE-FH60 & GE-FL60 installation scale?
Six cabinets connect in parallel, and up to 10 AC parallel groups extend the system to 500 kW and 3,600 kWh, with Black Start support included.
What climate suits the GE-FH60 & GE-FL60?
It operates from -30 to 60 degrees C with derating above 45 degrees, at 5-85% humidity and altitudes below 2,000 m; storage belongs between 0 and 35 degrees C.