Deye SUN-120/125/130/135/136K-G01P3-EU-AM8
120kW three phase string inverter with 98.8% efficiency and 8 MPPT channels.
Technical Specifications
| Parameter | SUN-120K-G01P3-EU-AM8 | SUN-125K-G01P3-EU-AM8 | SUN-130K-G01P3-EU-AM8 | SUN-135K-G01P3-EU-AM8 | SUN-136K-G01P3-EU-AM8 |
|---|---|---|---|---|---|
| Electrical / AC Output Data | |||||
| AC Output Overcurrent Protection | Yes | Yes | Yes | Yes | yes |
| AC Output Overvoltage Protection | Yes | Yes | Yes | Yes | yes |
| AC Output Short Circuit Protection | Yes | Yes | Yes | Yes | yes |
| DC Component Monitoring | Yes | Yes | Yes | Yes | yes |
| Max. AC Output Apparent Power (KVA) | 132 | 135 | 135 | 135 | 136 |
| Rated Output voltage/range (V) | 220/ | ||||
| AC Grid Connection Type | String Inverter | ||||
| Topology | Non-Isolated | ||||
| Max. AC Output Apparent Power | 132 kVA | 135 kVA | 135 kVA | 135 kVA | 136 kVA |
| Max. AC Output Current | 200/191.4 A | 204.6/195.7 A | 204.6/195.7 A | 204.6/195.7 A | 206.1/197.2 A |
| Adjustable Power Factor Range | 0.8 leading to 0.8 lagging | ||||
| Rated AC Output Current | 181.9/174 A | 189.4/181.2 A | 197/188.5 A | 204.6/195.7 A | 206.1/197.2 A |
| Rated Output Grid Frequency/Range | 50/45-55, 60/55-65 Hz | ||||
| Rated AC Power | 120 kW | 125 kW | 130 kW | 135 kW | 136 kW |
| European Efficiency | 98.2% | ||||
| THD / THDi | <3% | ||||
| Max Apparent Power | 132 kVA | 135 kVA | 135 kVA | 135 kVA | 136 kVA |
| Phase | Three-phase | ||||
| Additional Specifications | |||||
| DC Component of Grid | <0.5%In | ||||
| DC Injection Current | <0.5%In | ||||
| DC Polarity Reverse Connection Protection | Yes | ||||
| DC Terminal Insulation Impedance Monitoring | Yes | ||||
| Earth Fault Detection | Yes | ||||
| Full Load MPPT Voltage Range(V) | 550-850 | ||||
| Max. Input Short Circuit Current (A) | 60+60+60+60+60+60+60+60 | ||||
| Max. Output Fault Current (A) | 348 | ||||
| PV Input Voltage Range(V) | 250-1100 | ||||
| Max. Output Overcurrent Protection | 398 A | ||||
| Rated output voltage | 220/380V, 230/400V | ||||
| No. of Strings MPP Tracker | 4+4+4+4+4+4+4+4 | ||||
| Euro Efficiency | 98.2% | ||||
| Grid Connection Form | 3L/N/PE | ||||
| Ground Fault Current Monitoring | Yes | ||||
| Max. Inverter Backfeed Current To the Array | 0 | ||||
| Max. Operating PV Input Current | 40+40+40+40+40+40+40+40 A | ||||
| Monitor Mode | GPRS/WIFI/Bluetooth/4G/LAN(optional) | ||||
| Overvoltage Load Drop Protection | Yes | ||||
| Power Network Monitoring | Yes | ||||
| Rated Output Voltage/Range | 220/380V, 230/400V 0.85Un-1.1Un | ||||
| Residual Current (RCD) Detection | Yes | ||||
| Total Current Harmonic Distortion THDi | <3% | ||||
| Island Protection Monitoring | Yes | ||||
| Max PV Voltage | 1100 V | ||||
| Ingress Protection(IP) Rating | IP 65 | ||||
| Operating Temperature Range (°C) | -25 | ||||
| Permissible Altitude (m) | 4000m | ||||
| Noise | ≤65 dB(A) | ||||
| Operating Temperature Range | -25 to +60℃, >45℃ Derating °C | ||||
| Permissible Altitude | 4000 m | ||||
| DC Switch | yes | ||||
| DC reverse polarity protection | yes | ||||
| Electrical Data | |||||
| MPPT Voltage Range (V) | 200-1000 | ||||
| Max. AC Output Current (A) | 200/191.4 | 204.6/195.7 | 204.6/195.7 | 204.6/195.7 | 206.1/197.2 |
| Max. PV Input Power (kW) | 180 | 187.5 | 195 | 202.5 | 204 |
| Max. PV Input Voltage (V) | 1100 | ||||
| Max Efficiency | 98.8% | ||||
| No. of MPP Trackers/ No. of Strings MPP Tracker | 8/4+4+4+4+4+4+4+4 | ||||
| Rated AC Output Active Power (kW) | 120 | 125 | 130 | 135 | 136 |
| Rated AC Output Current (A) | 181.9/174.0 | 189.4/181.2 | 197/188.5 | 204.6/195.7 | 206.1/197.2 |
| Rated Output Grid Frequency/Range(Hz) | 50Hz/ | 50/45-55, 60/55-65 | 50/45-55, 60/55-65 | 50/45-55, 60/55-65 | 50/45-55, 60/55-65 |
| Rated PV Input Voltage (V) | 600 | ||||
| Start-up Voltage (V) | 250 | ||||
| PV Input Voltage Range | 250-1100 V | ||||
| Full Load MPPT Voltage Range | 550-850 V | ||||
| Max. Output Fault Current | 348 A | 362.4 A | 377 A | 391.4 A | 394.4 A |
| Rated AC Output Active Power | 120 kW | 125 kW | 130 kW | 135 kW | 136 kW |
| PV String Input Data | |||||
| Max. Operating PV Input Current(A) | 40 | ||||
| MPPT Efficiency | >99% | ||||
| MPPT Voltage Range | 200-1000 V | ||||
| Max. Input Short Circuit Current | 60+60+60+60+60+60+60+60 A | ||||
| Max. PV Input Power | 180 kW | 187.5 kW | 195 kW | 202.5 kW | 204 kW |
| Max. PV Input Voltage | 1100 V | ||||
| Rated PV Input Voltage | 600 V | ||||
| Start-up Voltage | 250 V | ||||
| Number of MPP Trackers | 8 | ||||
| Protection Features | |||||
| Anti-Islanding Protection | yes | ||||
| Grid Connection Standards | IEC 61727, IEC 62116,OVE-RichtlinieCEI0-21,R25,EN50549,G99,VDE-AR-NNRS097,RD4105140, UNE 217002, | ||||
| Overvoltage Category | OVC II(DC), OVC III(AC) | ||||
| Safety / EMC Standards | IEC/EN 61000-6-1/2/3/4, IEC/EN 62109-1, IEC/EN 62109-2 | ||||
| AC/DC Surge Protection | TYPE II(DC), TYPE II(AC) | ||||
| Over-Temperature / Thermal Protection | Yes | ||||
| IP Rating | IP65 | ||||
| Communication | |||||
| Communication Interface | RS485/RS232 /WiFi/LAN | ||||
| Mechanical Data | |||||
| Noise (dB) | ≤65 dB(A) | ||||
| Type Of Cooling | Intelligent air cooling | Intelligent Air Cooling | Intelligent Air Cooling | Intelligent Air Cooling | Intelligent air cooling |
| Cooling Method | Intelligent air cooling | Intelligent Air Cooling | Intelligent Air Cooling | Intelligent Air Cooling | Intelligent air cooling |
| Operating Conditions | |||||
| Noise Level | ≤65 dB | ||||
| Relative Humidity | 0-100% | ||||
| Operating Temperature | -25 to 60 °C | ||||
| Max Altitude | 4000 m | ||||
Figures are measured at the test conditions the manufacturer’s datasheet states. A dash means the manufacturer publishes no figure for that model.
Availability & grid compliance in Yemen
| Market | Yemen |
| Grid authority / regulator | Public Electricity Corporation (PEC), Ministry of Electricity and Energy |
| Quotation currency | YER |
| Support hours timezone | Asia/Aden |
| Delivery & installation coverage | Sana'a, Aden, Taiz, Al Hudaydah, Mukalla |
Figures on this page are the manufacturer's own, measured at the test conditions the datasheet states — they do not change by country. What changes is the approval that has to be met before the unit is energised: in Yemen that is Public Electricity Corporation (PEC), Ministry of Electricity and Energy. Confirm the grid code, import requirements and any local certification with them, or with us, before you order.
Key Features & Technical Highlights
- 98.8% Efficiency: Maximum energy conversion
- 8 MPPT Channels: Precise power optimization
- 180kW PV Input: Massive solar capacity
- Anti-PID: Protects panel performance
- VSG Support: Enhanced grid stability
- 4000m Altitude: High altitude operation
- 187.5kW PV Input: Massive solar capacity
- 195kW PV Input: Massive solar capacity
- 202.5kW PV Input: Massive solar capacity
- 204kW PV Input: Massive solar capacity
Frequently Asked Questions
Is the DEYE SUN-120K-G01P3-EU-AM8 suitable for the Middle East climate?
Yes. DEYE inverters are rated for high ambient temperatures and dusty conditions common across the Gulf, North Africa and the wider MEA region, with IP-rated enclosures for outdoor installation in shaded areas.
Why 8 MPPT channels?
Eight MPPT channels enable precise power optimization even under varying solar irradiation conditions, ensuring each solar panel string operates at its highest potential for maximum energy harvest.
What is the maximum PV input?
The SUN-120-136K series can handle up to 180kW of PV input power, allowing for very high DC/AC ratios and maximum energy production.