Deye GB-L-PRO
A floor-standing high-voltage stack of 4 kWh, 102.4 V modules reaching 8 to 24 kWh, IP65-sealed with explosion relief and fire protection built in.
Technical Specifications
| Parameter | DEYE-GB-L-PRO |
|---|---|
| Battery Data | |
| Energy | 4 kWh |
| Usable Energy | 7.2-21.6 kWh |
| Module Energy | 4 kWh |
| System Energy | 8-24 kWh |
| Nominal Voltage | 102.4 V |
| Module Nominal Voltage | 102.4 V |
| System Nominal Voltage | 204.8-614.4 V |
| Operating Voltage | 166.4-700.8 V |
| Rated Capacity | 40 Ah |
| Module Capacity | 40 Ah |
| Cell Chemistry | LiFePO4 |
| Cycle Life | >6000 |
| End-of-Life Capacity | 70% |
| Recommended Depth of Discharge | 90% |
| Max. Charge Current | 40 A |
| Max. Discharge Current | 40 A |
| Max. Charge/Discharge Current | 40 A |
| Nominal Charge/Discharge Current | 40 A |
| Recommended Charge/Discharge Current | 20 A |
| Peak Discharge Current | 50 (120s) A |
| Modules in Series | 2-6 |
| Min. Battery Module Quantity | 2 |
| Battery Module Models | GB-L8-Pro, GB-L12-Pro, GB-L16-Pro, GB-L20-Pro, GB-L24-Pro |
| Protection Features | Explosion Relief, Fire Protection |
| Warranty (Years) | 10 |
| Mechanical & Interface | |
| Communication Ports | CAN2.0, RS485 |
| Dimensions | 540 x 1530 x 385 mm |
| Additional Notes | Remote Updates |
| Module Dimensions | 540 x 220 x 385 mm |
| Module Weight | 39 kg |
| Status Indicator | LCD: SOC, Power, Total Voltage |
| Weight | 97-253 kg |
| Environment & Protection | |
| Altitude | <2000 m |
| Anti-Corrosion Grade | >C2 |
| Charge Temperature | -20 to 55 °C |
| Discharge Temperature | -20 to 55 °C |
| Operating Humidity | 5-90% |
| Installation Location | Floor-Mounted |
| Enclosure IP Rating | IP65 |
| Storage Temperature | 0-35 °C |
| Working Temperature | Charge: -20 to 55 / Discharge: -20 to 55 °C |
Figures are measured at the test conditions the manufacturer’s datasheet states. A dash means the manufacturer publishes no figure for that model.
Availability & grid compliance in Kuwait
| Market | Kuwait |
| Grid authority / regulator | MEW Kuwait |
| Quotation currency | KWD |
| Support hours timezone | Asia/Kuwait |
| Delivery & installation coverage | Kuwait City, Hawalli, Salmiya |
Figures on this page are the manufacturer's own, measured at the test conditions the datasheet states — they do not change by country. What changes is the approval that has to be met before the unit is energised: in Kuwait that is MEW Kuwait. Confirm the grid code, import requirements and any local certification with them, or with us, before you order.
Key Features & Technical Highlights
- 102.4 V in every module: Each 4 kWh module supplies 102.4 V, so two to six build 8 to 24 kWh at 204.8 to 614.4 V.
- Explosion relief built in: Explosion relief and fire protection are part of the pack design, not accessories.
- Skin graded for coasts: An anti-corrosion rating above C2 plus IP65 sealing stand up to humid, salty air.
- Charges at -20 degrees C: Both charge and discharge are rated across the -20 to 55 degrees C range.
- Updates without a visit: Remote firmware updates arrive over the CAN2.0 and RS485 links.
- A six-thousand-cycle core: LiFePO4 cells keep 70% capacity beyond 6,000 cycles, warranted 10 years.
Frequently Asked Questions
Why does the GB-L Pro need so few modules?
Because each module contributes 102.4 V and 4 kWh, two to six of them already form a 204.8 to 614.4 V system holding 8 to 24 kWh.
What safety hardware does the GB-L Pro carry?
Explosion relief and fire protection are engineered into the pack, complemented by an IP65 enclosure and an anti-corrosion grade above C2.
Is the GB-L Pro suitable near the sea?
Its corrosion resistance is graded above C2 and the housing is IP65-sealed, which is exactly the specification coastal humidity calls for.
What does the GB-L Pro display and report?
A front LCD shows state of charge, power and total voltage, while CAN2.0 and RS485 carry data, and remote updates, to the inverter side.
What are the GB-L Pro weight and current figures?
Modules weigh 39 kg each and towers 97 to 253 kg; current is 40 A continuous with a 50 A peak sustained for 120 seconds, 20 A being recommended.