Deye WS-GS2000-2H3
1MW/2057kWh utility-scale ESS in 20ft container with integrated PCS, MPPT, and dual fire protection.
Technical Specifications
| Parameter | DEYE-WS-GS2000-2H3 |
|---|---|
| Battery Data | |
| Battery Energy Capacity | 2057kWh |
| Battery Voltage Range | 819.2Vdc(691.2~921.6Vdc) |
| Round-Trip Efficiency | 88.50% |
| Nominal Capacity | 314Ah Cell |
| Battery Type / Chemistry | LiFePO₄ |
| Cell / Pack Configuration | 1P16S |
| Cycle Life | 8,000 (70% EOL) |
| Additional Specifications | |
| Battery parameter Cell type | LFP |
| Frequency/Range | 50Hz/45Hz-55Hz |
| Max. Apparent Power | 1100kVA |
| Rated PV Input Voltage | 600Vdc |
| Rated Voltage/Range | 400V/0.85Un-1.1Un |
| Total Current Harmonic Distortion | <3% (of Rated power) THDi |
| Nominal Voltage | 819.2 Vdc |
| PCS Output | 1 MW |
| No. of MPP Trackers | 64(8*8) |
| IP rating of enclosure | Anti-corrosion level |
| Dimension (W/D/H,mm) | 20ft (HC) |
| Container Size | 20ft (HC) |
| Operating ambient | -20~55 ℃ |
| Communication | |
| Communication Interface | RJ45 |
| Communication Protocol | Modbus TCP,IEC104,IEC61850 |
| PV String Input Data | |
| MPPT Voltage Range at Full Load | 450-750Vdc |
| MPPT Voltage Range | 180-750Vdc |
| Max PV Short-Circuit Current | 8×(60+60+60+60+60+60+60+60)A |
| Max PV Input Current | 8×(40+40+40+40+40+40+40+40)A |
| Max PV Input / Array Open Circuit Voltage | 800Vdc |
| Start-up Voltage | 200Vdc |
| Max PV Input Power | 1.6 MWp |
| Electrical / AC Output Data | |
| AC Grid Connection Type | 3L+N+PE |
| Max Efficiency | >99% |
| Adjustable Power Factor Range | 0.8 leading-0.8lagging |
| Overload Capability | 1.1x/1.5x |
| Mechanical Data | |
| Cooling | Air cooling |
| Design / Form Factor | Floor mount |
| Protection Features | |
| IP Rating | IP54 (C4-M) |
| Operating Conditions | |
| Max Altitude | 3000m |
| Relative Humidity | 0 ~ 90 |
| Storage Temperature Range | -20~60 °C |
| Operating Temperature | -20 to 50 °C |
Figures are measured at the test conditions the manufacturer’s datasheet states. A dash means the manufacturer publishes no figure for that model.
Availability & grid compliance in Sudan
| Market | Sudan |
| Grid authority / regulator | Sudanese Electricity Distribution Company (SEDC), Ministry of Energy and Petroleum |
| Quotation currency | SDG |
| Support hours timezone | Africa/Khartoum |
| Delivery & installation coverage | Khartoum, Omdurman, Port Sudan, Kassala, Nyala |
Figures on this page are the manufacturer's own, measured at the test conditions the datasheet states — they do not change by country. What changes is the approval that has to be met before the unit is energised: in Sudan that is Sudanese Electricity Distribution Company (SEDC), Ministry of Energy and Petroleum. Confirm the grid code, import requirements and any local certification with them, or with us, before you order.
Key Features & Technical Highlights
- 1MW PCS: Megawatt-scale power
- 2057kWh Energy: Massive storage capacity
- Dual Fire Protection: Gas + water systems
- Smart Cloud: 24/7 O&M, custom algorithms
- 420kW DC Charge: Fast EV charging support
- 20ft Container: Turnkey solution
Frequently Asked Questions
Is the DEYE WS-GS2000-2H3 suitable for hot climates like the Gulf?
Yes. The WS-GS2000-2H3 uses LiFePO4 chemistry with a BMS and thermal management designed to operate safely in the high ambient temperatures common across the Middle East and Africa.
What applications is this suitable for?
The WS-GS2000-2H3 is ideal for utility-scale applications including black start, off-grid operation/backup, peak shaving, transformer capacity control, virtual power plants, and EV charging infrastructure.
What fire protection does it have?
The system features 2-hour fire resistance with dual protection: combustible gas detection, smoke evacuation, aerosol extinguishers, and water sprinklers for comprehensive fire safety.