Deye SUN-10/12/15K-G05-LV
10kW three phase string inverter (LV) with 98.6% efficiency and smart monitoring.
Technical Specifications
| Parameter | DEYE-SUN-10K-G05-LV | DEYE-SUN-12K-G05-LV | DEYE-SUN-15K-G05-LV |
|---|---|---|---|
| Additional Specifications | |||
| Arc fault circuit interrupter (AFCI) | Optional | ||
| MPPT Voltage Range(V) | 200-700 | ||
| Max. Input Short Circuit Current (A) | 39+39 | ||
| Max. Operating PV Input Current(A) | 26+26 | ||
| Max. PV Input Voltage(V) | 800 | ||
| PV Input Voltage Range(V) | 250-800 | ||
| Rated PV Input Voltage(V) | 500 | ||
| PV Input Voltage Range | 250-800 V | 250-800 V | 250-1000 V |
| No. of Strings MPP Tracker | 2+2 | ||
| No. of MPP Trackers | 2 | ||
| Grid Connection Form | 3L/N/PE | ||
| Ground Fault Current Monitoring | Yes | ||
| Max. Inverter Backfeed Current To the Array | 0 | ||
| Monitor Mode | GPRS/WIFI/Bluetooth/4G/LAN(optional) | ||
| Overvoltage Load Drop Protection | Yes | ||
| Power Network Monitoring | Yes | ||
| Rated Output Grid Frequency/Range | 50/45-55, 60/55-65 Hz | ||
| Rated Output Voltage/Range | 127V/220V, 133V/230V 0.85UN-1.1UN | ||
| Residual Current (RCD) Detection | Yes | ||
| Max PV Voltage | 800 V | ||
| DC Injection Current | <0.5%In | ||
| DC Polarity Reverse Connection Protection | Yes | ||
| DC Terminal Insulation Impedance Monitoring | Yes | ||
| DC Component Monitoring | yes | ||
| Ingress Protection(IP) Rating | IP 65 | ||
| Operating Temperature Range | -25 to +60℃, >45℃ Derating °C | ||
| Earth Fault Detection | Yes Yes Yes Yes Yes Yes Yes | ||
| DC Reverse Polarity Protection | Yes | ||
| AC Output Overvoltage Protection | Yes | ||
| AC Output Short Circuit Protection | Yes | ||
| Island Protection Monitoring | Earth Fault Detection Yes Yes Yes Yes Yes Yes Yes | ||
| Electrical / AC Output Data | |||
| Full Load MPPT Voltage Range(V) | 250-700 | 300-700 | 375-700 |
| Max. Output Fault Current (A) | 50.2 | 60.2 | 75.2 |
| Max. Output Overcurrent Protection (A) | 76.9 | 76.9 | 85 |
| Max. PV Input Power(kW) | 13 | 15.6 | 19.5 |
| Max.AC Output Current(A) | 26.3/25.1 | 31.5/30.1 | 39.4/37.6 |
| Rated AC Output Active Power(kW) | 10 | 12 | 15 |
| Rated Output voltage/range (V) | 127V/ | 220V, 133V/230V 0.85Un-1.1 | — |
| AC Grid Connection Type | String Inverter | ||
| European Efficiency | 98.0% | ||
| Topology | Non-Isolated | ||
| Max. AC Output Apparent Power | 10 kVA | 12 kVA | 15 kVA |
| Max. AC Output Current | 26.3/25.1 A | 31.5/30.1 A | 39.4/37.6 A |
| Adjustable Power Factor Range | 0.8 leading to 0.8 lagging | ||
| Rated AC Output Current | 26.3/25.1 A | 31.5/30.1 A | 39.4/37.6 A |
| THD / THDi | <3% | ||
| Rated AC Power | 10 kW | 12 kW | 15 kW |
| Nominal AC Voltage | 127V/220V, 133V/230V | ||
| Rated AC Input/Output Active Power | 10000 W | 12000 W | — |
| Max. AC Input/Output Apparent Power | 11000 VA | 13200 VA | — |
| Rated AC Input/Output Current | 15.2/14.5 A | 18.2/17.4 A | — |
| Max. AC Input/Output Current | 16.7/15.9 A | 20/19.1 A | — |
| Max. Three-phase Unbalanced Output Current | 22.7/21.7 A | 27.3/26.1 A | — |
| Max Continuous AC Pass-Through | 45 A | ||
| Max. Output Overcurrent Protection | 70 A | 70 A | 47.7 A |
| Electrical Data | |||
| Max. Efficiency | 98.5% | ||
| No. of MPP Trackers/ No. of Strings MPP Tracker | 2/2+2 | ||
| Rated AC Output current (A) | 26.3/25.1 | 31.5/30.1 | 39.4/37.6 |
| Start-up Voltage(V) | 250 | ||
| Full Load MPPT Voltage Range | 250-700 V | 300-700 V | 375-700 V |
| Max. Output Fault Current | 50.2 A | 60.2 A | 75.2 A |
| Rated AC Output Active Power | 10 kW | 12 kW | 15 kW |
| Max.AC Output Apparent Power(KVA) | 16.5 | ||
| Rated Output Grid Frequency/range(Hz) | 50Hz/45Hz-55Hz, 60Hz/55Hz-65Hz | ||
| Protection Features | |||
| Anti-Islanding Protection | yes | ||
| Grid Connection Standards | NBR 16149, NBR 16150, EN 50549, RD 140 | ||
| Overvoltage Category | OVC II(DC), OVC III(AC) | ||
| Safety / EMC Standards | IEC/EN 61000-6-1/2/3/4, IEC/EN 62109-1, IEC/EN 62109-2 | ||
| AC/DC Surge Protection | TYPE II(DC), TYPE II(AC) | ||
| Over-Temperature / Thermal Protection | Yes | ||
| IP Rating | IP65 | ||
| Communication | |||
| Communication Interface | RS485/RS232 /WiFi/LAN | ||
| PV String Input Data | |||
| MPPT Efficiency | >99% | ||
| MPPT Voltage Range | 200-700 V | ||
| Max. Input Short Circuit Current | 39+39 A | ||
| Max. Operating PV Input Current | 26+26 A | ||
| Max. PV Input Power | 13 kW | 15.6 kW | 19.5 kW |
| Max. PV Input Voltage | 800 V | ||
| Rated PV Input Voltage | 500 V | ||
| Start-up Voltage | 250 V | ||
| Mechanical Data | |||
| Type Of Cooling | Intelligent air cooling | ||
| Cooling Method | Intelligent air cooling | ||
| Operating Conditions | |||
| Noise Level | ≤50 dB | ||
| Max Altitude | 4000 m | ||
| Relative Humidity | 0-100% | ||
| Operating Temperature | -25 to 60 °C | ||
Figures are measured at the test conditions the manufacturer’s datasheet states. A dash means the manufacturer publishes no figure for that model.
Availability & grid compliance in Yemen
| Market | Yemen |
| Grid authority / regulator | Public Electricity Corporation (PEC), Ministry of Electricity and Energy |
| Quotation currency | YER |
| Support hours timezone | Asia/Aden |
| Delivery & installation coverage | Sana'a, Aden, Taiz, Al Hudaydah, Mukalla |
Figures on this page are the manufacturer's own, measured at the test conditions the datasheet states — they do not change by country. What changes is the approval that has to be met before the unit is energised: in Yemen that is Public Electricity Corporation (PEC), Ministry of Electricity and Energy. Confirm the grid code, import requirements and any local certification with them, or with us, before you order.
Key Features & Technical Highlights
- 98.6% Efficiency: Maximum energy conversion
- Smart Monitoring: String-level performance tracking
- Zero Export: Grid export limit compliance
- VSG Support: Virtual Synchronous Generator
- Multiple Comms: GPRS, WiFi, Bluetooth, 4G, LAN
- IP65 Protection: Weather resistant design
Frequently Asked Questions
Is the DEYE SUN-10K-G05-LV suitable for the Middle East climate?
Yes. DEYE inverters are rated for high ambient temperatures and dusty conditions common across the Gulf, North Africa and the wider MEA region, with IP-rated enclosures for outdoor installation in shaded areas.
What voltage systems is this compatible with?
The SUN-10K-G05-LV supports 127V/220V and 133V/230V systems at 50/60Hz, making it versatile for various grid configurations.
Does it support string-level monitoring?
Yes! Optional string intelligent monitoring provides real-time insight into individual string performance for efficient maintenance and troubleshooting.