Deye SUN-100/110/70/75/80/90K-G03
100kW three phase string inverter with 98.8% efficiency and 6 MPPT channels.
Technical Specifications
| Parameter | DEYE-SUN-100K-G03 | DEYE-SUN-110K-G03 | DEYE-SUN-70K-G03 | DEYE-SUN-75K-G03 | DEYE-SUN-80K-G03 | DEYE-SUN-90K-G03 |
|---|---|---|---|---|---|---|
| Electrical / AC Output Data | ||||||
| AC Output Active Power(kW) | 100 | 110 | 70 | 75 | 80 | 90 |
| AC Output current (A) | 151.5/144.9 | 166.7/159.4 | 106.1/101.5 | 113.6/108.7 | 121.2/115.9 | 136.4/130.4 |
| Output Current(A) | 166.7/159.4 | 183.3/175.4 | 116.7/111.6 | 125/119.6 | 133.3/127.5 | 150/143.5 |
| Output Fault Current (A) | 289.8 | 318.8 | 203 | 217.4 | 231.8 | 260.8 |
| Output Overcurrent Protection (A) | 286 | 286 | 206 | 206 | 206 | 286 |
| Max. Output Fault Current (A) | 289.8 | 318.8 | 203 | 217.4 | 231.8 | 260.8 |
| Max. Output Overcurrent Protection (A) | 286 | 286 | 206 | 206 | 206 | 286 |
| Max. PV Input Power(kW) | 150 | 150 | 91 | 97.5 | 104 | 135 |
| Max.AC Output Current(A) | 166.7/159.4 | 183.3/175.4 | 116.7/111.6 | 125/119.6 | 133.3/127.5 | 150/143.5 |
| Rated AC Output Active Power(kW) | 100 | 110 | 70 | 75 | 80 | 90 |
| Euro Efficiency | 98.2% | 98.2% | 98.1% | 98.1% | 98.1% | 98.2% |
| Max.AC Output Apparent Power | 110 kVA | 121 kVA | — | — | — | — |
| Max Efficiency | 98.8% | 98.8% | 98.7% | 98.7% | 98.7% | 98.8% |
| Adjustable Power Factor Range | 0.8 leading-0.8lagging | |||||
| Rated AC Output Current | 151.5/144.9 A | 166.7/159.4 A | 106.1/101.5 113.6/108.7 121.2/115.9 136.4/130.4151.5/144.9166.7/159.4 A | 106.1/101.5 113.6/108.7 121.2/115.9 136.4/130.4151.5/144.9166.7/159.4 A | 106.1/101.5 113.6/108.7 121.2/115.9 136.4/130.4151.5/144.9166.7/159.4 A | 136.4/130.4 A |
| Rated Output Grid Frequency/range | 50Hz/45Hz-55Hz, 60Hz/55Hz-65 | 50Hz/45Hz-55Hz, 60Hz/55Hz-65 | 50Hz/45Hz-55Hz, 60Hz/55Hz-65Hz | 50Hz/45Hz-55Hz, 60Hz/55Hz-65Hz | 50Hz/45Hz-55Hz, 60Hz/55Hz-65Hz | 50Hz/45Hz-55Hz, 60Hz/55Hz-65Hz |
| Surge Protection Level | TYPE II(DC),TYPE II(AC) | TYPE II(DC),TYPE II(AC) | TYPE II(DC), TYPE II(AC) | TYPE II(DC), TYPE II(AC) | TYPE II(DC), TYPE II(AC) | TYPE II(DC),TYPE II(AC) |
| Rated AC Power | 100000 W | 110000 W | 70000 W | 75000 W | 80000 W | 90000 W |
| European Efficiency | 98.2% | |||||
| THD / THDi | <3% | |||||
| Phase | 3L/N/PE | |||||
| Nominal AC Voltage | 220/380V, 230/400V | |||||
| Max.AC Output Apparent Power(KVA | — | — | 77 | 82.5 | 88 | 99 |
| Additional Specifications | ||||||
| DC Injection Current | <0.5% | |||||
| Full Load MPPT Voltage Range(V) | 550-850 | |||||
| MPPT Voltage Range(V) | 200-850 | |||||
| Max. PV Input Voltage(V) | 1000 | |||||
| PV Input Voltage Range(V) | 250-1000 | |||||
| Rated AC Output current (A) | 151.5/144.9 | 166.7/159.4 | 106.1/101.5 | 113.6/108.7 | 121.2/115.9 | 136.4/130.4 |
| Rated PV Input Voltage(V) | 600 | |||||
| PV Input Voltage Range | 250-1000 V | 250-1000 V | 250-1100 V | 250-1100 V | 250-1100 V | 250-1000 V |
| Type | String Inverter | |||||
| Max PV Voltage | 1000 | |||||
| No. of Strings MPP Tracker | 4+4+4+4+4+4 | |||||
| No. of MPP Trackers/ No. of Strings MPP Tracker | 6/4+4+4+4+4+4 | |||||
| Grid Connection Form | 3L+N+PE | |||||
| Max. Input Short Circuit Current | 60+60+60+60+60+60 A | |||||
| Max. Inverter Backfeed Current To the Array | 0 | |||||
| Max. Operating PV Input Current | 40+40+40+40+40+40 A | |||||
| Max.AC Output Current | 166.7/159.4 A | 183.3/175.4 A | 116.7/111.6 A | 125/119.6133.3/127.5 A | 125/119.6133.3/127.5 A | 150/143.5 A |
| Rated Output voltage/range | 220/380V, 230/400V 0.85Un-1.1Un | |||||
| Residual Current Detection | yes | |||||
| Total Current Harmonic Distortion THDi | <3% | |||||
| Communication Interface | RS485/RS232 | |||||
| Grid Regulation | UNEIEC61727,217002,IECOVE-Richtlinie62116,CEI0-21,R25,CEIG99,0-16,VDE-AR-NEN50549,4105,NRSVDE-AR-N097,RD140,4110 | |||||
| Inverter Topology | Non-Isolated | |||||
| Over Voltage Category | OVC II(DC),OVC III(AC) | |||||
| Safety EMC/Standard | IEC/EN 61000-6-1/2/3/4, IEC/EN 62109-1, IEC/EN 62109-2 | |||||
| Monitor Mode | GPRS/WIFI/Bluetooth/4G/LAN(optional) | |||||
| Ingress Protection(IP) Rating | IP 65 | |||||
| Type Of Cooling | Intelligent air cooling | |||||
| Operating Temperature Range | -25℃ to +60℃,>45℃ derating °C | |||||
| Permissible Altitude | 4000 m | |||||
| Permissible Ambient Humidity | 0-100% | |||||
| No. of MPP Trackers | 6 | |||||
| Weight [kg] | 81 | |||||
| Electrical Data | ||||||
| Start-up Voltage(V) | 250 | |||||
| Max. Output Overcurrent Protection | 286 A | 286 A | 206 A | 206 A | 206 A | 286 A |
| Full Load MPPT Voltage Range | 550-850 V | |||||
| Max. Output Fault Current | 289.8 A | 318.8 A | 203 A | 217.4 A | 231.8 A | 260.8 A |
| Rated AC Output Active Power | 100 kW | 110 kW | 70 kW | 75 kW | 80 kW | 90 kW |
| Protection Features | ||||||
| Anti-Islanding Protection | yes | |||||
| Over-Temperature / Thermal Protection | yes | |||||
| IP Rating | IP65 | |||||
| AC/DC Surge Protection | TYPE II(DC), TYPE II(AC) | |||||
| PV String Input Data | ||||||
| MPPT Efficiency | >99% | |||||
| MPPT Voltage Range | 200-850 V | |||||
| Max. PV Input Power | 150 kW | 150 kW | 91 kW | 97.5 kW | 104 kW | 135 kW |
| Max. PV Input Voltage | 1000 V | |||||
| Rated PV Input Voltage | 600 V | |||||
| Start-up Voltage | 250 V | |||||
| Number of MPP Trackers | 6 | 6 | 4 | 4 | 4 | 6 |
| Max PV Input Current | 40+40+40+40 A | |||||
| Max PV Short-Circuit Current | 60+60+60+60 A | |||||
| Mechanical Data | ||||||
| Cooling | Intelligent Air Cooling | |||||
| Operating Environment | ||||||
| Noise | ≤55 dB | ≤55 dB | ≤ 55 dB | ≤ 55 dB | ≤ 55 dB | ≤ 55 dB |
| Operating Conditions | ||||||
| Operating Temperature | -25 to 60 °C | |||||
| Max Altitude | 4000 m | |||||
Figures are measured at the test conditions the manufacturer’s datasheet states. A dash means the manufacturer publishes no figure for that model.
Availability & grid compliance in Yemen
| Market | Yemen |
| Grid authority / regulator | Public Electricity Corporation (PEC), Ministry of Electricity and Energy |
| Quotation currency | YER |
| Support hours timezone | Asia/Aden |
| Delivery & installation coverage | Sana'a, Aden, Taiz, Al Hudaydah, Mukalla |
Figures on this page are the manufacturer's own, measured at the test conditions the datasheet states — they do not change by country. What changes is the approval that has to be met before the unit is energised: in Yemen that is Public Electricity Corporation (PEC), Ministry of Electricity and Energy. Confirm the grid code, import requirements and any local certification with them, or with us, before you order.
Key Features & Technical Highlights
- 98.8% Efficiency: Maximum energy conversion
- 6 MPPT Channels: Optimal string performance
- Anti-PID: Protects panel performance
- VSG Support: Virtual Synchronous Generator
- 4000m Altitude: High altitude operation
- Multiple Monitoring: GPRS, WiFi, Bluetooth, 4G, LAN
Frequently Asked Questions
Is the DEYE SUN-100K-G03 suitable for the Middle East climate?
Yes. DEYE inverters are rated for high ambient temperatures and dusty conditions common across the Gulf, North Africa and the wider MEA region, with IP-rated enclosures for outdoor installation in shaded areas.
What is the maximum PV input power?
The SUN-100K-G03 series can handle up to 150kW of PV input power, allowing for high DC/AC ratios and maximum energy harvest.
Can this inverter operate at high altitude?
Yes! The inverter is rated for operation up to 4000m altitude, making it suitable for installations in mountainous regions.