An integrated solar-storage station in a 20-ft high-cube container: 2,057 kWh of storage, 1,280 kW of PV capacity, 64 MPPTs and utility-grade grid communications.
Technical Specifications
| Parameter | DEYE-WS-GS2000-2H3 |
|---|---|
| Battery Data | |
| Energy | 2057 kWh |
| Nominal Voltage | 819.2 V |
| System Nominal Voltage | 819.2 V |
| Operating Voltage | 691.2-921.6 V |
| Rated Voltage Range | 400/0.85Un-1.1Un V |
| Rated Capacity | 314 Ah |
| Module Capacity | 314 Ah |
| Cell Chemistry | LiFePO4 |
| Pack Configuration | 1P16S |
| Cycle Life | >6000 |
| Rated DC Power | 1000 kW |
| Max. Round-Trip Efficiency | 88.5% |
| Max. Efficiency | >99% |
| Min. Battery Module Quantity | 1 |
| Protection Features | Combustible Gas Detection, Smoke Evacuation, 2h Fire Resistance |
| Grid Connection Form | 3L+N+PE |
| Peak Power (Off-Grid) | 1.1x/1.5x of rated power |
| Power Factor | 0.8 Leading-0.8 Lagging |
| Total Harmonic Distortion (THD) | <3 (of rated power)% |
| Frequency Range | 50/45-55 Hz |
| AC Rated Current | 1443 (180.4 per unit) A |
| Max. Apparent Power | 1100 kVA |
| Full-Load MPPT Voltage Range | 450-750 V |
| Max. Input Short-Circuit Current | 3840 (60 per mppt) A |
| Max. Operating PV Input Current | 2560 (40 per mppt) A |
| Max. PV Input Power | 1280 (160 per unit) kW |
| Max. PV Input Voltage | 800 V |
| Number of MPPTs | 64 (8 x 8) |
| MPPT Voltage Range | 180-750 V |
| Rated PV Input Voltage | 600 V |
| Startup Voltage | 200 V |
| Mechanical & Interface | |
| Communication Ports | RJ45 |
| Communication Protocol | Modbus TCP, IEC104, IEC61850 |
| Dimensions | 20ft (HC) mm |
| Weight | <26000 kg |
| Environment & Protection | |
| Altitude | <3000 m |
| Anti-Corrosion Grade | C4-M |
| Fire Suppression | Gas, Water |
| Operating Humidity | 0-90% |
| Installation Location | Floor-Mounted |
| Enclosure IP Rating | IP54 |
| Storage Temperature | -20 to 60 °C |
| Cooling Type | Air Cooling |
| Working Temperature | -20 to 55 °C |
Figures are measured at the test conditions the manufacturer’s datasheet states. A dash means the manufacturer publishes no figure for that model.
Availability & grid compliance in Oman
| Market | Oman |
| Grid authority / regulator | Authority for Electricity Regulation Oman |
| Quotation currency | OMR |
| Support hours timezone | Asia/Muscat |
| Delivery & installation coverage | Muscat, Salalah, Sohar |
Figures on this page are the manufacturer's own, measured at the test conditions the datasheet states — they do not change by country. What changes is the approval that has to be met before the unit is energised: in Oman that is Authority for Electricity Regulation Oman. Confirm the grid code, import requirements and any local certification with them, or with us, before you order.
Key Features & Technical Highlights
- A plant in a box: 2,057 kWh of LiFePO4 storage at 819.2 V nominal inside one 20-ft high-cube container weighing under 26,000 kg.
- 1,280 kW of PV intake: 64 MPPTs (8 x 8) track from 180 to 750 V, with 800 V maximum input and full-load range of 450-750 V.
- 1,100 kVA of output: 1,000 kW rated DC power onto a 400 V, 3L+N+PE connection at 50 Hz, with THD under 3%.
- Engineered fire safety: Gas and water suppression, combustible-gas detection, smoke evacuation and 2-hour fire resistance.
- Speaks utility SCADA: Modbus TCP, IEC104 and IEC61850 over RJ45 for plant-level control.
- 88.5% round-trip efficiency: Maximum efficiency exceeds 99%, with off-grid peak output of 1.1x and 1.5x rated power.
Frequently Asked Questions
What scale of project suits the WS-GS2000-2H3?
Utility and large commercial-industrial plants: each container carries 2,057 kWh of storage, 1,280 kW of PV input and 1,100 kVA of output capability.
Does the WS-GS2000-2H3 need separate inverters?
Power conversion is part of the container: it delivers up to 1,100 kVA at 400 V (3L+N+PE, 50 Hz) with THD below 3% and a 0.8 leading to 0.8 lagging power factor.
How does the WS-GS2000-2H3 talk to plant control systems?
Over RJ45 using Modbus TCP, IEC104 and IEC61850 - the protocols utility SCADA systems expect.
What fire protection is built into the WS-GS2000-2H3?
Gas and water fire suppression, combustible-gas detection, smoke evacuation and a 2-hour fire-resistance rating.
What site conditions does the container tolerate?
Working temperatures of -20 to 55 degrees Celsius, 0-90% humidity and altitudes below 3,000 m, with an IP54 enclosure and C4-M anti-corrosion grade.