Deye WS-GS2000-2H3
An integrated solar-storage station in a 20-ft high-cube container: 2,057 kWh of storage, 1,280 kW of PV capacity, 64 MPPTs and utility-grade grid communications.
Technical Specifications
| Parameter | DEYE-WS-GS2000-2H3 |
|---|---|
| Battery Data | |
| Energy | 2057 kWh |
| Nominal Voltage | 819.2 V |
| System Nominal Voltage | 819.2 V |
| Operating Voltage | 691.2-921.6 V |
| Rated Voltage Range | 400/0.85Un-1.1Un V |
| Rated Capacity | 314 Ah |
| Module Capacity | 314 Ah |
| Cell Chemistry | LiFePO4 |
| Pack Configuration | 1P16S |
| Cycle Life | >6000 |
| Rated DC Power | 1000 kW |
| Max. Round-Trip Efficiency | 88.5% |
| Max. Efficiency | >99% |
| Min. Battery Module Quantity | 1 |
| Protection Features | Combustible Gas Detection, Smoke Evacuation, 2h Fire Resistance |
| Grid Connection Form | 3L+N+PE |
| Peak Power (Off-Grid) | 1.1x/1.5x of rated power |
| Power Factor | 0.8 Leading-0.8 Lagging |
| Total Harmonic Distortion (THD) | <3 (of rated power)% |
| Frequency Range | 50/45-55 Hz |
| AC Rated Current | 1443 (180.4 per unit) A |
| Max. Apparent Power | 1100 kVA |
| Full-Load MPPT Voltage Range | 450-750 V |
| Max. Input Short-Circuit Current | 3840 (60 per mppt) A |
| Max. Operating PV Input Current | 2560 (40 per mppt) A |
| Max. PV Input Power | 1280 (160 per unit) kW |
| Max. PV Input Voltage | 800 V |
| Number of MPPTs | 64 (8 x 8) |
| MPPT Voltage Range | 180-750 V |
| Rated PV Input Voltage | 600 V |
| Startup Voltage | 200 V |
| Mechanical & Interface | |
| Communication Ports | RJ45 |
| Communication Protocol | Modbus TCP, IEC104, IEC61850 |
| Dimensions | 20ft (HC) mm |
| Weight | <26000 kg |
| Environment & Protection | |
| Altitude | <3000 m |
| Anti-Corrosion Grade | C4-M |
| Fire Suppression | Gas, Water |
| Operating Humidity | 0-90% |
| Installation Location | Floor-Mounted |
| Enclosure IP Rating | IP54 |
| Storage Temperature | -20 to 60 °C |
| Cooling Type | Air Cooling |
| Working Temperature | -20 to 55 °C |
Figures are measured at the test conditions the manufacturer’s datasheet states. A dash means the manufacturer publishes no figure for that model.
Availability & grid compliance in Yemen
| Market | Yemen |
| Grid authority / regulator | Public Electricity Corporation (PEC), Ministry of Electricity and Energy |
| Quotation currency | YER |
| Support hours timezone | Asia/Aden |
| Delivery & installation coverage | Sana'a, Aden, Taiz, Al Hudaydah, Mukalla |
Figures on this page are the manufacturer's own, measured at the test conditions the datasheet states — they do not change by country. What changes is the approval that has to be met before the unit is energised: in Yemen that is Public Electricity Corporation (PEC), Ministry of Electricity and Energy. Confirm the grid code, import requirements and any local certification with them, or with us, before you order.
Key Features & Technical Highlights
- A plant in a box: 2,057 kWh of LiFePO4 storage at 819.2 V nominal inside one 20-ft high-cube container weighing under 26,000 kg.
- 1,280 kW of PV intake: 64 MPPTs (8 x 8) track from 180 to 750 V, with 800 V maximum input and full-load range of 450-750 V.
- 1,100 kVA of output: 1,000 kW rated DC power onto a 400 V, 3L+N+PE connection at 50 Hz, with THD under 3%.
- Engineered fire safety: Gas and water suppression, combustible-gas detection, smoke evacuation and 2-hour fire resistance.
- Speaks utility SCADA: Modbus TCP, IEC104 and IEC61850 over RJ45 for plant-level control.
- 88.5% round-trip efficiency: Maximum efficiency exceeds 99%, with off-grid peak output of 1.1x and 1.5x rated power.
Frequently Asked Questions
What scale of project suits the WS-GS2000-2H3?
Utility and large commercial-industrial plants: each container carries 2,057 kWh of storage, 1,280 kW of PV input and 1,100 kVA of output capability.
Does the WS-GS2000-2H3 need separate inverters?
Power conversion is part of the container: it delivers up to 1,100 kVA at 400 V (3L+N+PE, 50 Hz) with THD below 3% and a 0.8 leading to 0.8 lagging power factor.
How does the WS-GS2000-2H3 talk to plant control systems?
Over RJ45 using Modbus TCP, IEC104 and IEC61850 - the protocols utility SCADA systems expect.
What fire protection is built into the WS-GS2000-2H3?
Gas and water fire suppression, combustible-gas detection, smoke evacuation and a 2-hour fire-resistance rating.
What site conditions does the container tolerate?
Working temperatures of -20 to 55 degrees Celsius, 0-90% humidity and altitudes below 3,000 m, with an IP54 enclosure and C4-M anti-corrosion grade.