A 215 kWh storage cabinet that charges straight from a 200 kW solar array, dispatching 100 kW of rated power and scaling to twenty paralleled units for large sites.
Technical Specifications
| Parameter | DEYE-MS-GS215-2H3 |
|---|---|
| Battery Data | |
| Energy | 215 kWh |
| System Energy | 215 kWh |
| Max. Capacity | 4300 kWh |
| Nominal Voltage | 51.2 V |
| Operating Voltage | 660-864 V |
| Rated Capacity | 280 Ah |
| Cell Chemistry | LiFePO4 |
| Cycle Life | >6000 |
| End-of-Life Capacity | 70% |
| Rated DC Power | 100 kW |
| Max. Round-Trip Efficiency | 88% |
| Max. Efficiency | 97.6% |
| Min. Battery Module Quantity | 1 |
| Parallel Units | 20 |
| Overvoltage Protection | DC Type II, AC Type II |
| Grid Connection Form | 3L+N+PE |
| Peak Power (Off-Grid) | 1.1x of rated power |
| Power Factor | -1 to 1 |
| Total Harmonic Distortion (THD) | <3% |
| AC Rated Current | 152 A |
| Max. AC Output Current | 167 A |
| Full-Load MPPT Voltage Range | 450-750 V |
| Max. PV Input Power | 200 kW |
| Max. PV Input Voltage | 800 V |
| MPPT Voltage Range | 180-750 V |
| Startup Voltage | 200 V |
| Mechanical & Interface | |
| Communication Ports | ETH/4G |
| Dimensions | 1865 x 2500 x 1000 mm |
| Additional Notes | DC Injection Current: <0.5ln; AC Output Frequency and Voltag; Crane-hoisted |
| Status Indicator | LCD |
| Weight | 2732 kg |
| Environment & Protection | |
| Altitude | <3000 m |
| Anti-Corrosion Grade | C5 |
| Operating Humidity | 15-85 (non-condensing)% |
| Installation Location | Floor-Mounted (foundation) |
| Enclosure IP Rating | IP54 |
| Working Temperature | -20 to 50 °C |
Figures are measured at the test conditions the manufacturer’s datasheet states. A dash means the manufacturer publishes no figure for that model.
Availability & grid compliance in UAE
| Market | UAE |
| Grid authority / regulator | DEWA, ADDC, SEWA |
| Quotation currency | AED |
| Support hours timezone | Asia/Dubai |
| Delivery & installation coverage | Dubai, Abu Dhabi, Sharjah, Ajman, Ras Al Khaimah |
Figures on this page are the manufacturer's own, measured at the test conditions the datasheet states — they do not change by country. What changes is the approval that has to be met before the unit is energised: in UAE that is DEWA, ADDC, SEWA. Confirm the grid code, import requirements and any local certification with them, or with us, before you order.
Key Features & Technical Highlights
- Direct 200 kW solar input: PV connects at up to 800 V, with MPPT tracking from 180 to 750 V and a 200 V startup voltage.
- 215 kWh dispatchable reserve: LiFePO4 cells of 280 Ah hold 215 kWh, dispatched at 100 kW of rated DC power.
- Scales to 4,300 kWh: Twenty cabinets parallel together, toward a stated maximum capacity of 4,300 kWh.
- C5 coastal corrosion grade: An IP54 enclosure with C5 anti-corrosion rating stands up to aggressive marine air.
- Clean 3L+N+PE grid tie: AC output runs at a rated 152 A and up to 167 A, with harmonic distortion under 3% and 97.6% maximum efficiency.
- Crane-hoisted foundation install: The 2,732 kg cabinet, at 1865 x 2500 x 1000 mm, is lifted by crane onto a prepared foundation.
Frequently Asked Questions
How much solar can the MS-GS215-2H3 take directly?
Its PV input accepts up to 200 kW at a maximum of 800 V, with an MPPT range of 180-750 V, a full-load MPPT window of 450-750 V and a 200 V startup voltage.
How does the MS-GS215-2H3 differ from a plain storage cabinet?
It charges its 215 kWh reserve straight from the array through built-in MPPT tracking, then feeds a 3L+N+PE grid connection at up to 167 A - no separate solar inverter in between.
What is the maximum size of an MS-GS215-2H3 installation?
Up to 20 units operate in parallel, and the stated maximum capacity is 4,300 kWh.
Is the MS-GS215-2H3 suitable for coastal sites?
Yes - its enclosure combines an IP54 rating with a C5 anti-corrosion grade, the class specified for aggressive coastal atmospheres.
What does installing the MS-GS215-2H3 involve?
The cabinet weighs 2,732 kg, measures 1865 x 2500 x 1000 mm and is crane-hoisted onto a foundation; it then operates from -20 to 50 degrees C below 3,000 m altitude.