DEYE SUN-8K-SG05LP1-EU Hybrid Inverter
DEYE MJS

SUN-8K-SG05LP1-EU

8kW single phase hybrid inverter with 190A charging and 16 units parallel.

  • Power Range: 8 kW
  • Max Charge Current: 190 A
6,135 AEDincl. VAT
Full Specifications

Features

190A Charging

Ultra-high battery charging

16 Units Parallel

Scale up to 128kW

AC Coupling

Retrofit existing systems

Touch LCD Display

Colorful intuitive interface

IP65 Protection

Outdoor rated installation

Generator Support

Store diesel generator energy

Overview

The Deye SUN-8K-SG05LP1-EU series delivers state-of-the-art energy management for residential and small commercial installations. With 8kW power range, 190A max charging/discharging, 97.6% max efficiency, 40-60V battery support, 16 units parallel capability, AC coupling for retrofits, and IP65 protection, it's the versatile choice for optimizing energy storage and consumption.

Full specifications

Electrical

DC Injection Current<0.5% In
MPPT Voltage Range (V)150-425
Max. PV Input Voltage (V)500
Peak Power (off-grid) (W), 10s
Rated PV Input Voltage (V)370
Start-up Voltage (V)125
Max PV Voltage500
Max. Charging/Discharging Current190
Grid Frequency50/45-55, 60/55-65
TypeHybrid Inverter
No. of Strings MPP Tracker2+2
Max. Output Fault Current(A)80
Peak Power (off-grid)(W)2
No. of MPP Trackers/No. of Strings MPP Tracker2/2+2
Full Load MPPT Voltage Range(V)250-425
PV Input Voltage Range(V)125-500
Battery TypeLead-acid or Lithium-ion
Battery Voltage Range40-60 V
Charging Strategy for Li-ion BatterySelf-adaption to BMS
Communication InterfaceWIFI,RS485,CAN
Euro Efficiency96.5%
Grid Connection FormL+N+PE
Grid RegulationIEC 61727, IECOVE-Richtlinie62116,CEI0-21,R25,ENG98,50549,G99,NRSVDE-AR-N097,RD4105140, UNE 217002,
Inverter TopologyNon-Isolated
LCD/LED DisplayLCD
MPPT Efficiency>99%
MPPT Voltage Range150-425 V
Max. AC Input/Output Apparent Power8800 VA
Max. AC Input/Output Current40/38.3 A
Max. Charging Current190 A
Max. Continuous AC Passthrough (grid to load)50 A
Max. Discharging Current190 A
Max. Efficiency97.6%
Max. Input Short-Circuit Current34+34 A
Max. Operating PV Input Current26+26 A
Max. PV Access Power16000 W
Max. PV Input Power12800 W
Max. PV Input Voltage500 V
Number of Battery Input1
Over Voltage CategoryOVC II(DC), OVC III(AC)
Power Factor Adjustment Range0.8 leading to 0.8 lagging
Rated AC Input/Output Active Power8000 W
Rated AC Input/Output Current36.4/34.8 A
Rated Input/Output Grid Frequency/Range50/45-55, 60/55-65 Hz
Rated Input/Output Voltage/Range220/230 0.85Un-1.1Un V
Rated PV Input Voltage370 V
Safety / EMC StandardIEC/EN 61000-6-1/2/3/4, IEC/EN 62109-1, IEC/EN 62109-2
Start-up Voltage125 V
Surge Protection LevelTYPE II(DC), TYPE II(AC)
Total Current Harmonic Distortion THDi<3% (of nominal power)
Peak Power (off-grid)2 times of rated power, 10s W
Rated AC Power8000 W
Max Charge Current190 A
MPPT Trackers2
Max Parallel Units16 pcs
PhaseSingle-phase

Mechanical

Type of CoolingIntelligent Air Cooling
Ingress Protection(IP) RatingIP 65
IP RatingIP65
CoolingIntelligent Air Cooling
Noise Level<30 dB
DisplayColorful Touch LCD

Environmental

Noise<45 dB
Operating Temperature Range-40 to +60℃, >45℃ Derating ℃
Permissible Altitude2000m
Permissible Ambient Humidity0-100%
Operating Temperature-40 to 60 °C
Humidity0-100 %
Max Altitude2000 m

Certifications

  • IEC 61727
  • IEC 62116
  • CEI 0-21

Troubleshooting & error codes

Looking up an error code on this Deye SUN LP1 Hybrid Series? Browse the full list of codes for this device, with the cause and recommended fix for each.

View error codes for this device →

Related Products