W03Warning

DEYE inverter error W03

Arc warning

Warningthe red LED flashes and the inverter keeps running. Deal with it before it escalates.

The exact meaning depends on your model:

Also applies to:SUN-120K-G01P3-EU-BM8SUN-125K-G01P3-EU-BM8SUN-130K-G01P3-EU-BM8SUN-135K-G01P3-EU-BM8SUN-136K-G01P3-EU-BM8SUN-60K-G03SUN-70K-G03SUN-75K-G03+12

What it means

Arc warningAn arc issue was detected on the PV side of the inverter.

Cause: An electrical arc has formed on the PV side, usually at a poor or loose PV string connection.

How to fix it

Check the connection of the PV, then clear the fault through the ARC function in the operating parameters; the inverter can then resume operation.

Source: 041_BManual_SUN-120_125_130_135_136K-G01P3-EU-BM8_20251021_en_a2166559.pdf, p.60 · 033_BManual_SUN-70_75_80_90_100_110K-G03_20260702_en_a9db1e1b.pdf, p.59 · 042_BManual_SUN-120_125_130_135_136K-G01P3-EU-AM8_20260702_en_05f936e3.pdf, p.59 · +2 more official manuals

Also applies to:SUN-6K-G06-LV-P1SUN-8K-G06-LV-P1SUN-6K-G06P3-EU-BM2-LV-P1SUN-8K-G06P3-EU-BM2-LV-P1SUN-10K-G05-LVSUN-12K-G05-LVSUN-15K-G05-LVSUN-15K-G06P3-EU-BM2-P1+27

What it means

Arc warningWarning that the PV side of the inverter has caused an arc issue.

Cause: An arc was detected on the PV side of the inverter, usually from a loose or poor PV connection.

How to fix it

Check the connection of the PV, then clear this fault through the ARC function in the operating parameters; the inverter can then resume operation.

Source: 063_BManual_SUN-6K-G06-LV-P1_20250923_en_30a96699.pdf, p.56

Also applies to:SUN-5K-SG01HP3-EU-AM2SUN-6K-SG01HP3-EU-AM2SUN-8K-SG01HP3-EU-AM2SUN-10K-SG01HP3-EU-AM2SUN-12K-SG01HP3-EU-AM2SUN-15K-SG01HP3-EU-AM2SUN-20K-SG01HP3-EU-AM2SUN-25K-SG01HP3-EU-AM2+9

What it means

Grid Phase WarningGrid_phase_warn - the phase sequence detected at the grid connection is abnormal.

Cause: The phase sequence connection of the power grid is incorrect, or the configured grid type does not match the actual grid.

How to fix it

  1. Check the phase sequence connection of the power grid
  2. Try to change the grid type (e.g. 240/120)
  3. If there is still no solution, check the wiring at the grid end.

Source: 037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf, p.48 · 050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf, p.49 · 062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf, p.49

Frequently asked questions

What does error W03 mean on a DEYE inverter?
It depends on the model — 4 devices use code W03. On the SUN G01P3-EU-BM8 Series it means: Arc warning. The card for each model on this page gives its exact meaning and fix.
Is error W03 a fault or a warning?
W03 is a warning: the red LED flashes and the unit keeps running. Fix the underlying condition before it escalates.
How do I clear or fix error W03?
Check the connection of the PV, then clear the fault through the ARC function in the operating parameters; the inverter can then resume operation. The exact steps for each affected model are listed on this page.