34Fault

DEYE inverter error 34 (F034)

AC current over load

Also displayed as F034 / F34 on some models.

Faultthe inverter cuts its output and the red LED stays solid until the fault is cleared.

The exact meaning depends on your model:

Also applies to:SUN-120K-G01P3-EU-BM8SUN-125K-G01P3-EU-BM8SUN-130K-G01P3-EU-BM8SUN-135K-G01P3-EU-BM8SUN-136K-G01P3-EU-BM8SUN-7K-G02P1-EU-AM2SUN-7.5K-G02P1-EU-AM2SUN-8K-G02P1-EU-AM2+3

What it means

AC current over loadThe AC output current stayed above the rated level (overload). The manual notes this code has hardly ever appeared in the field.

Cause: The AC output current stayed above the rated level long enough to trip the overload protection.

How to fix it

Restart the inverter; if the code persists after the restart, contact your installer or Deye service and provide the inverter serial number, the installation date and the displayed error code.

Source: 041_BManual_SUN-120_125_130_135_136K-G01P3-EU-BM8_20251021_en_a2166559.pdf, p.62 · 065_BManual_SUN-7_7.5_8K-G02P1-EU-AM2_20260625_en_4466f08b.pdf, p.52 · 032_BManual_SUN-9_10_10.5K-G02P1-EU-AM2_20260625_en_df0f2106.pdf, p.52

Also applies to:SUN-60K-G03SUN-70K-G03SUN-75K-G03SUN-80K-G03SUN-90K-G03SUN-100K-G03SUN-110K-G03SUN-60K-G01P3-EU-AM8-LV+7

What it means

AC current over loadThe AC output current stayed above the rated level (overload).

Cause: The AC output current stayed above the rated level long enough to trip the overload protection.

How to fix it

Restart the inverter; if the fault is not ruled out, contact the installer or the manufacturer's customer service.

Source: 033_BManual_SUN-70_75_80_90_100_110K-G03_20260702_en_a9db1e1b.pdf, p.62 · 042_BManual_SUN-120_125_130_135_136K-G01P3-EU-AM8_20260702_en_05f936e3.pdf, p.61 · 060_BManual_SUN-60_70_75K-G01P3-EU-AM8-LV_20260701_en_f559aeec.pdf, p.61 · +1 more official manuals

Also applies to:SUN-6K-G06-LV-P1SUN-8K-G06-LV-P1SUN-6K-G06P3-EU-BM2-LV-P1SUN-8K-G06P3-EU-BM2-LV-P1SUN-10K-G05-LVSUN-12K-G05-LVSUN-15K-G05-LVSUN-15K-G06P3-EU-BM2-P1+27

What it means

AC current over loadThe AC output current exceeded the rated load (overload).

Cause: The load or output current stayed above the inverter's rated current.

How to fix it

Restart the inverter; if the fault is not ruled out, contact the installer or manufacturer customer service.

Source: 063_BManual_SUN-6K-G06-LV-P1_20250923_en_30a96699.pdf, p.58

Also applies to:SUN-1K-G04P1-EU-AM1SUN-1.5K-G04P1-EU-AM1SUN-2K-G04P1-EU-AM1SUN-2.2K-G04P1-EU-AM1SUN-2.5K-G04P1-EU-AM1SUN-2.7K-G04P1-EU-AM1SUN-3K-G04P1-EU-AM1SUN-3.3K-G04P1-EU-AM1+36

What it means

AC current over loadThe AC output current exceeded the rated load (overload).

Cause: The load or output current stayed above the inverter's rated current.

How to fix it

Deye states this code has hardly ever appeared in the field; contact your installer or Deye service if it occurs.

Source: 031_BManual_SUN-1_1.5_2_2.2_2.5_2.7_3_3.3_3.6_4K-G04P1-EU-AM1_20260624_en_15adc00c.pdf, p.54 · 036_BManual_SUN-3_4_5_6_7_8_9_10_12_15K-G06P3-EU-BM2_20250506_en_0eb78440.pdf, p.57

Also applies to:SUN-3.6K-SG05LP1-EU-SM2-PSUN-5K-SG05LP1-EU-SM2-PSUN-6K-SG05LP1-EU-SM2-PSUN-7K-SG05LP1-EU-SM2-PSUN-7.6K-SG05LP1-EU-SM2-PSUN-8K-SG05LP1-EU-SM2-PSUN-10K-SG05LP1-EU-SM2-PSUN-7.6K-SG01LP1-EU+21

What it means

AC Overcurrent faultAC overcurrent fault on the backup load output.

Cause: The connected backup load exceeds the allowed power range.

How to fix it

  1. Check the backup load connected and make sure it is in the allowed power range.
  2. If the fault still exists, contact Deye for help.

Source: 039_BManual_SUN-3.6_5_6_7_7.6_8_10K-SG05LP1-EU-SM2-P_20260428_en_70c401a6.pdf, p.50 · 043_BManual_SUN-12_14_16K-SG01LP1-EU_20260519_en_703e15ac.pdf, p.46 · 052_BManual_SUN-_3.6-6_K-OG01LP1-EU-AM2_20260406_en_dc31b173.pdf, p.46 · +4 more official manuals

Also applies to:SUN-5K-SG01HP3-EU-AM2SUN-6K-SG01HP3-EU-AM2SUN-8K-SG01HP3-EU-AM2SUN-10K-SG01HP3-EU-AM2SUN-12K-SG01HP3-EU-AM2SUN-15K-SG01HP3-EU-AM2SUN-20K-SG01HP3-EU-AM2SUN-25K-SG01HP3-EU-AM2+9

What it means

AC Overload FaultAC_Overload_Fault - the backup load exceeds the allowed power.

Cause: The load connected to the backup (Load) port exceeds the allowed power range.

How to fix it

Check the backup load connection and make sure it is within the allowed power range.

Source: 037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf, p.50 · 050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf, p.51 · 062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf, p.51

Also applies to:SUN-5K-SG02LP2-US-AM2SUN-6K-SG02LP2-US-AM2SUN-7.6K-SG02LP2-US-AM2SUN-8K-SG02LP2-US-AM2SUN-10K-SG02LP2-US-AM3SUN-12K-SG02LP2-US-AM3SUN-5K-SG04LP3-EUSUN-6K-SG04LP3-EU+15

What it means

AC Overcurrent FaultAC Overcurrent fault - the backup load exceeds the allowed power.

Cause: The load connected to the backup port exceeds the allowed power range.

How to fix it

  1. Check the backup load connected and make sure it is in the allowed power range
  2. If the fault still exists, contact us for help.

Source: 059_BManual_SUN-5_6_7.6_8_10_12K-SG02LP2-US-AM2_AM3_20260406_en_fb6a30c7.pdf, p.55 · 038_BManual_SUN-5_6_8_10_12K-SG04LP3-EU_20260319_en_081932c1.pdf, p.47 · 040_BManual_SUN-3_4_5_6_8_10_12K-SG05LP3-EU-SM2_20260319_en_b0183b7d.pdf, p.47 · +1 more official manuals

AI-W5.1 ESS

Energy storage systemFault

Also applies to:AI-W5.1-5P3-EU-B-ESSAI-W5.1-6P3-EU-B-ESSAI-W5.1-8P3-EU-B-ESSAI-W5.1-10P3-EU-B-ESSAI-W5.1-12P3-EU-B-ESS

What it means

AC Overcurrent faultAC overload fault on the backup output.

Cause: The backup load power exceeded the allowed output power range.

How to fix it

  1. Check the connected backup load and make sure it is within the allowed power range.
  2. If the fault still exists, contact Deye for help.

Source: 002_Download_4e90fe7a.pdf, p.47

GB-SL / GB-SL Pro ESS

Energy storage systemFault

Also applies to:GB-SL5K-EUGB-SL6K-EUGB-SL8K-EUGB-SL10K-EUGB-SL12K-EUGB-SL15K-EUGB-SL20K-EUGB-SL Pro 5K-EU+6

What it means

AC_Overload_FaultAC overload fault on the backup output.

Cause: The backup load power exceeded the allowed output power range.

How to fix it

  1. Check the backup load connection and make sure it is within the allowed power range.
  2. If the fault still exists, contact Deye for help.

Source: 081_deye_gb_sl_pro_user_manual_46fa941a.pdf, p.50 · 010_Download_cc05df18.pdf, p.45

GB-A HV Battery

BatteryFault

Also applies to:GB-A

What it means

ALARM_ID_BAT_VOLT_SAMP_ERRORAbnormal internal total-voltage sampling.

Cause: The internal pack total-voltage measurement returned an invalid reading - a sampling-circuit or harness fault.

How to fix it

  1. Restart the system.
  2. If the fault persists, contact Deye support for service.

Source: 008_deye_ess_user_manual_gb_a_jpnen_v02_20250829_3fea617e.pdf, p.14

Frequently asked questions

What does error 34 mean on a DEYE inverter?
It depends on the model — 13 devices use code 34. On the SUN G01P3-EU-BM8 Series it means: AC current over load. The card for each model on this page gives its exact meaning and fix.
Is error 34 a fault or a warning?
34 is a fault code: the inverter cuts its output and the red LED stays solid until it is cleared.
How do I clear or fix error 34?
Restart the inverter; if the code persists after the restart, contact your installer or Deye service and provide the inverter serial number, the installation date and the displayed error code. The exact steps for each affected model are listed on this page.

Related error codes

Prefer the full written guide? Read the complete DEYE inverter error-code guide

Compiled from official DEYE user manuals. Always consult your device manual and a qualified technician before performing repairs.