Deye 10.5 kW Single-Phase String Solar Inverter SUN-10.5K-G02P1-EU-AM2
- Rated AC Output Active Power:10500 W
- Max. Efficiency:97.7 %
This is the complete fault table for the Deye SUN G02P1-EU Series Inverter family — 64 codes shared by 6 model numbers, transcribed from the official manual. On Deye units, a fault code means the unit has cut its output and the red LED stays solid; a warning flashes the red LED while the unit keeps running.
Last checked against the official manuals on 11 July 2026.






The DC input from the PV strings is connected with reversed polarity.
CauseThe plus and minus conductors of a PV string are swapped at the inverter's DC input, so the inverter sees reverse polarity.
Recommended fixCheck the PV input polarity.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 50sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 50
The insulation impedance between the DC (PV) side and ground is permanently below the protection limit.
CauseA defective or missing inverter ground connection, or degraded DC-side insulation, keeps the measured insulation impedance to ground below the limit.
Recommended fixCheck the grounding cable of the inverter.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 50sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 50
Leakage current on the DC side exceeds the protection limit. The manual notes this code has hardly ever appeared in the field.
CauseLeakage current from the DC side to ground exceeds the protection threshold, typically caused by damaged PV cable or module insulation.
Recommended fixRestart the inverter; if the code persists after the restart, contact your installer or Deye service and provide the inverter serial number, the installation date and the displayed error code.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 50sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 50
The ground-fault detector/interrupter (GFDI) has detected a ground fault on the PV side.
CauseA PV output conductor is faulted to ground, tripping the GFDI protection.
Recommended fixCheck the solar panel output connection.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 50sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 50
Failure in reading the internal memory (EEPROM).
CauseThe controller failed to read stored data from the EEPROM memory chip.
Recommended fixRestart the inverter; if the fault still exists, contact your installer or Deye service.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 50sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 50
Failure in writing the internal memory (EEPROM).
CauseThe controller failed to write data to the EEPROM memory chip.
Recommended fixRestart the inverter; if the fault still exists, contact your installer or Deye service.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 50sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 50
The GFDI protection fuse has blown. The manual notes this code has hardly ever appeared in the field.
CauseThe ground-fault detector/interrupter fuse has blown, which points to a ground-fault current having flowed on the PV side.
Recommended fixRestart the inverter; if the code persists after the restart, contact your installer or Deye service and provide the inverter serial number, the installation date and the displayed error code.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 50sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 50
The GFDI circuit reports a failed grounding contact. The manual notes this code has hardly ever appeared in the field.
CauseThe GFDI circuit detected a failed ground contact, so the ground-fault protection path is not intact.
Recommended fixRestart the inverter; if the code persists after the restart, contact your installer or Deye service and provide the inverter serial number, the installation date and the displayed error code.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 50sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 50
An IGBT power switch shows an excessive voltage drop. The manual notes this code has hardly ever appeared in the field.
CauseAn IGBT power switch exhibits an excessive on-state voltage drop, indicating the switch has been damaged.
Recommended fixRestart the inverter; if the code persists after the restart, contact your installer or Deye service and provide the inverter serial number, the installation date and the displayed error code.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 50sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 50
The internal auxiliary switching power supply has failed; the DC 12 V rail is missing. The manual notes this code has hardly ever appeared in the field.
CauseThe auxiliary switching power supply inside the inverter has failed, so an internal supply rail is missing.
Recommended fixRestart the inverter; if the code persists after the restart, contact your installer or Deye service and provide the inverter serial number, the installation date and the displayed error code.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 51sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 51
The main AC contactor did not operate correctly. The manual notes this code has hardly ever appeared in the field.
CauseThe main AC contactor failed to switch as commanded or returned an implausible feedback state.
Recommended fixRestart the inverter; if the code persists after the restart, contact your installer or Deye service and provide the inverter serial number, the installation date and the displayed error code.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 51sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 51
The auxiliary AC contactor did not operate correctly. The manual notes this code has hardly ever appeared in the field.
CauseThe auxiliary AC contactor failed to switch as commanded or returned an implausible feedback state.
Recommended fixRestart the inverter; if the code persists after the restart, contact your installer or Deye service and provide the inverter serial number, the installation date and the displayed error code.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 51sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 51
The working mode or grid mode of the inverter changed. The manual notes this code has hardly ever appeared in the field.
CauseThe inverter's working mode or grid mode setting was changed while it was operating.
Recommended fixRestart the inverter; if the code persists after the restart, contact your installer or Deye service and provide the inverter serial number, the installation date and the displayed error code.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 51sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 51
Firmware-level DC over-current protection tripped. The manual notes this code has hardly ever appeared in the field.
CauseThe DC input current exceeded the firmware (software) over-current limit.
Recommended fixRestart the inverter; if the code persists after the restart, contact your installer or Deye service and provide the inverter serial number, the installation date and the displayed error code.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 51sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 51
Firmware-level AC over-current protection tripped.
CauseThe AC output current exceeded the firmware limit; the internal AC sensor, its detection circuit on the control board, or a connection wire may be loose.
Recommended fix1. Check the internal AC sensor, its detection circuit on the control board and the connection wiring. 2. Restart the inverter; if the error still exists, contact your installer or Deye service.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 51sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 51
The GFCI/RCD stage measured an average AC leakage current above the protection threshold.
CauseThe average AC leakage current measured by the GFCI/RCD stage exceeds the protection threshold, from a real leakage path on the DC supply or solar panels or from a faulty leakage current sensor or its circuit.
Recommended fix1. Check whether the DC power supply and the solar panels are OK, then check the 'Test data' -> 'diL' value, then check the leakage current sensor and its circuit (viewing test data requires the big LCD). 2. Restart the inverter; if the error still exists, contact your installer or Deye service.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 51sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 51
The three-phase output current exceeded the over-current protection limit. The manual notes this code has hardly ever appeared in the field.
CauseThe summed three-phase output current exceeded the over-current protection limit.
Recommended fixRestart the inverter; if the code persists after the restart, contact your installer or Deye service and provide the inverter serial number, the installation date and the displayed error code.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 51sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 51
Hardware-level AC over-current protection tripped.
CauseThe AC output current exceeded the hardware protection limit; the AC sensor or its detection circuit on the control board, or the connection wiring, may be faulty.
Recommended fix1. Check the AC sensor and its detection circuit on the control board and the connection wiring. 2. Restart the inverter or perform a factory reset; if the error still exists, contact your installer or Deye service.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 51sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 51
Aggregate flag for combined hardware protection faults; on these models it can be triggered by hot-plugging the WiFi logger.
CausePlugging the WiFi logger in while the inverter is running raises F19; otherwise it is the aggregate flag for combined hardware protection trips.
Recommended fixRestart the inverter or perform a factory reset; if the error still exists, contact your installer or Deye service.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 51sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 51
Hardware-level DC over-current protection tripped. Marked 'Not available' in the manual for these models.
CauseHardware-level DC input over-current protection; this code is not used on these single-phase models.
Recommended fixMarked 'Not available' in the manual - this code is not used on these models. if it is displayed nonetheless, restart the inverter and contact your installer or Deye service.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 51sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 51
Leakage current in the DC circuit exceeded the protection threshold. The manual notes this code has hardly ever appeared in the field.
CauseLeakage current in the DC circuit exceeded the protection threshold.
Recommended fixRestart the inverter; if the code persists after the restart, contact your installer or Deye service and provide the inverter serial number, the installation date and the displayed error code.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 51sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 51
The inverter performed a crash (emergency) stop.
CauseThe external stop button (where fitted) was activated, forcing the inverter to stop immediately.
Recommended fixContact your installer for help.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 51sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 51
The AC leakage current rose above the transient protection threshold suddenly.
CauseThe leakage current suddenly jumped above the transient protection threshold, from a real transient leakage path on the DC supply or solar panels or from a faulty leakage current sensor or its circuit.
Recommended fix1. Check whether the DC power supply and the solar panels are OK, then check the 'Test data' -> 'diL' value, then check the leakage current sensor and its circuit (checking test data requires the big LCD). 2. Restart the inverter; if the fault still exists, contact your installer or Deye service.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 51sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 51
The PV-array-to-ground insulation impedance is too low.
CauseThe insulation impedance between the PV array and ground is too low: often a PV panel problem, poor grounding of the PV panel frames or of the inverter, or an AC/DC cable or terminal block shorted to ground or with damaged insulation.
Recommended fix1. Check the Vpe resistance on the main board and its detection on the control board, and check that the PV panels are OK - many times this issue is a PV problem. 2. Check that the PV panel aluminium frames and the inverter are grounded well; open the inverter cover and check that the inside ground cable is fixed well on the shell. 3. Check whether an AC/DC cable or terminal block is shorted to ground or has damaged insulation. 4. Restart the inverter; if the fault still exists, contact your installer or Deye service.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 51sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 51
Current was detected feeding back into the DC side. The manual notes this code has hardly ever appeared in the field.
CauseCurrent was detected flowing back into the DC side (DC feedback/backfeed).
Recommended fixRestart the inverter; if the code persists after the restart, contact your installer or Deye service and provide the inverter serial number, the installation date and the displayed error code.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 51sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 51
The voltages on the two halves of the DC bus are unbalanced. The manual notes this code has hardly ever appeared in the field.
CauseThe voltages on the two halves of the DC bus drifted apart beyond the allowed unbalance.
Recommended fixRestart the inverter; if the code persists after the restart, contact your installer or Deye service and provide the inverter serial number, the installation date and the displayed error code.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 51sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 51
An insulation error was detected at the DC end. The manual notes this code has hardly ever appeared in the field.
CauseThe insulation at the DC end of the power stage fell below the acceptable level.
Recommended fixRestart the inverter; if the code persists after the restart, contact your installer or Deye service and provide the inverter serial number, the installation date and the displayed error code.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 52sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 52
The DC component on inverter bridge 1 is too high. The manual notes this code has hardly ever appeared in the field.
CauseThe DC component measured on inverter bridge 1 is too high.
Recommended fixRestart the inverter; if the code persists after the restart, contact your installer or Deye service and provide the inverter serial number, the installation date and the displayed error code.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 52sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 52
The AC load switch failed. The manual notes this code has hardly ever appeared in the field.
CauseThe AC load switch failed to operate correctly.
Recommended fixRestart the inverter; if the code persists after the restart, contact your installer or Deye service and provide the inverter serial number, the installation date and the displayed error code.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 52sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 52
The main AC relay/contactor failed to operate.
CauseThe main AC relay failed to close correctly: a relay fault, a relay driver circuit fault, or software that is not suitable for this inverter (old inverters have no relay detection function).
Recommended fix1. Check the relays and the AC voltage of the relays. 2. Check the relay driver circuit. 3. Check if the software is not suitable for this inverter (old inverters have no relay detection function). 4. Restart the inverter; if the fault still exists, contact your installer or Deye service.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 52sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 52
DC boost soft-start fault. Marked 'Not available' in the manual for these models.
CauseFault of the DC boost soft-start stage; this code is not used on these single-phase models.
Recommended fixMarked 'Not available' in the manual - this code is not used on these models. if it is displayed nonetheless, restart the inverter and contact your installer or Deye service.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 52sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 52
The DC component on inverter bridge 2 is too high. The manual notes this code has hardly ever appeared in the field.
CauseThe DC component measured on inverter bridge 2 is too high.
Recommended fixRestart the inverter; if the code persists after the restart, contact your installer or Deye service and provide the inverter serial number, the installation date and the displayed error code.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 52sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 52
AC over-current reported by the current measurement.
CauseThe AC current sensor or its circuit has an issue, or the configured inverter type does not match the machine.
Recommended fixCheck the AC current sensor and its circuit; check whether the inverter type setting is right for this machine.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 52sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 52
The AC output current stayed above the rated level (overload). The manual notes this code has hardly ever appeared in the field.
CauseThe AC output current stayed above the rated level long enough to trip the overload protection.
Recommended fixRestart the inverter; if the code persists after the restart, contact your installer or Deye service and provide the inverter serial number, the installation date and the displayed error code.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 52sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 52
No grid voltage is detected.
CauseNo AC grid voltage is present at the inverter: a grid outage, a bad AC connector or cable, or a fault in the AC voltage detection circuit.
Recommended fix1. Check the AC grid voltage and the AC voltage detection circuit; check that the AC connector is in good condition and that the AC grid is normal in voltage. 2. Restart the inverter; if the fault still exists, contact your installer or Deye service.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 52sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 52
A grid phase error was detected. The manual notes this code has hardly ever appeared in the field.
CauseThe grid phase sequence or phase angle is wrong, or a phase reference was lost.
Recommended fixRestart the inverter; if the code persists after the restart, contact your installer or Deye service and provide the inverter serial number, the installation date and the displayed error code.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 52sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 52
The three grid phase voltages are unbalanced. The manual notes this code has hardly ever appeared in the field.
CauseThe three grid phase voltages are unbalanced beyond the allowed range.
Recommended fixRestart the inverter; if the code persists after the restart, contact your installer or Deye service and provide the inverter serial number, the installation date and the displayed error code.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 52sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 52
The three output phase currents are unbalanced. The manual notes this code has hardly ever appeared in the field.
CauseThe three output phase currents are unbalanced beyond the allowed range.
Recommended fixRestart the inverter; if the code persists after the restart, contact your installer or Deye service and provide the inverter serial number, the installation date and the displayed error code.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 52sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 52
AC over-current detected within one grid cycle.
CauseThe AC output current exceeded the limit within a single grid cycle; the AC current sensor or its circuit may be faulty.
Recommended fix1. Check the AC current sensor and its circuit. 2. Restart the inverter; if the fault still exists, contact your installer or Deye service.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 52sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 52
The DC input current exceeded the over-current protection limit. The manual notes this code has hardly ever appeared in the field.
CauseThe DC input current exceeded the over-current protection limit.
Recommended fixRestart the inverter; if the code persists after the restart, contact your installer or Deye service and provide the inverter serial number, the installation date and the displayed error code.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 52sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 52
The W-U line voltage is above the protection setting.
CauseThe line voltage between phases W and U exceeds the protection setting; an AC cable that is too thin raises the voltage at the inverter terminals under feed-in.
Recommended fixCheck the AC voltage protection setting, and check if the AC cable is too thin. Check the voltage difference between the LCD and a meter.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 52sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 52
The W-U line voltage is below the protection setting.
CauseThe line voltage between phases W and U is below the protection setting; loose or incorrectly connected AC cables can cause the low reading.
Recommended fixCheck the AC voltage protection setting. Check the voltage difference between the LCD and a meter, and check whether all AC cables are firmly and correctly connected.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 52sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 52
The V-W line voltage is above the protection setting. Marked 'Not available' in the manual for these models.
CauseLine voltage protection between phases V and W - a three-phase measurement that is not used on these single-phase models.
Recommended fixMarked 'Not available' in the manual - this code is not used on these models. if it is displayed nonetheless, restart the inverter and contact your installer or Deye service.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 52sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 52
The V-W line voltage is below the protection setting. Marked 'Not available' in the manual for these models.
CauseLine voltage protection between phases V and W - a three-phase measurement that is not used on these single-phase models.
Recommended fixMarked 'Not available' in the manual - this code is not used on these models. if it is displayed nonetheless, restart the inverter and contact your installer or Deye service.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 52sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 52
The U-V line voltage is above the protection setting. Marked 'Not available' in the manual for these models.
CauseLine voltage protection between phases U and V - a three-phase measurement that is not used on these single-phase models.
Recommended fixMarked 'Not available' in the manual - this code is not used on these models. if it is displayed nonetheless, restart the inverter and contact your installer or Deye service.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 52sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 52
The U-V line voltage is below the protection setting. Marked 'Not available' in the manual for these models.
CauseLine voltage protection between phases U and V - a three-phase measurement that is not used on these single-phase models.
Recommended fixMarked 'Not available' in the manual - this code is not used on these models. if it is displayed nonetheless, restart the inverter and contact your installer or Deye service.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 52sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 52
The grid frequency is above the protection setting.
CauseThe measured grid frequency is above the configured protection limit.
Recommended fixCheck the frequency protection setting.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 52sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 52
The grid frequency is below the protection setting.
CauseThe measured grid frequency is below the configured protection limit.
Recommended fixCheck the frequency protection setting.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 52sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 52
The DC component of the U-phase grid current is too high. The manual notes this code has hardly ever appeared in the field.
CauseThe DC component of the U-phase grid current exceeds the allowed limit.
Recommended fixRestart the inverter; if the code persists after the restart, contact your installer or Deye service and provide the inverter serial number, the installation date and the displayed error code.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 52sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 52
The DC component of the V-phase grid current is too high. The manual notes this code has hardly ever appeared in the field.
CauseThe DC component of the V-phase grid current exceeds the allowed limit.
Recommended fixRestart the inverter; if the code persists after the restart, contact your installer or Deye service and provide the inverter serial number, the installation date and the displayed error code.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 52sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 52
The DC component of the W-phase grid current is too high. The manual notes this code has hardly ever appeared in the field.
CauseThe DC component of the W-phase grid current exceeds the allowed limit.
Recommended fixRestart the inverter; if the code persists after the restart, contact your installer or Deye service and provide the inverter serial number, the installation date and the displayed error code.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 53sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 53
The DC current through AC filter inductor phase A is too high. The manual notes this code has hardly ever appeared in the field.
CauseThe DC current component through AC filter inductor phase A exceeds the allowed limit.
Recommended fixRestart the inverter; if the code persists after the restart, contact your installer or Deye service and provide the inverter serial number, the installation date and the displayed error code.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 53sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 53
The DC current through AC filter inductor phase B is too high. The manual notes this code has hardly ever appeared in the field.
CauseThe DC current component through AC filter inductor phase B exceeds the allowed limit.
Recommended fixRestart the inverter; if the code persists after the restart, contact your installer or Deye service and provide the inverter serial number, the installation date and the displayed error code.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 53sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 53
The DC current through AC filter inductor phase C is too high. The manual notes this code has hardly ever appeared in the field.
CauseThe DC current component through AC filter inductor phase C exceeds the allowed limit.
Recommended fixRestart the inverter; if the code persists after the restart, contact your installer or Deye service and provide the inverter serial number, the installation date and the displayed error code.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 53sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 53
The DC bus voltage is above the limit.
CauseThe DC bus (Ubus) voltage is above the limit - usually the PV input voltage is too high because too many solar panels are connected in series, or the Ubus detection circuit is faulty.
Recommended fix1. Check the PV voltage and the Ubus voltage and their detection circuit; if the PV input voltage exceeds the limit, reduce the number of solar panels in series. 2. For the Ubus voltage, check the LCD display.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 53sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 53
The DC bus voltage is below the limit.
CauseThe PV input voltage is low - it always happens in the early morning; if F56 appears while the inverter is running, a loss of the driver or firmware that needs updating may be responsible.
Recommended fix1. Check the PV voltage and the Ubus voltage - in the early morning this normally just reflects low PV input voltage. 2. if it shows while the inverter is running, the driver may have been lost or the firmware may need updating. 3. Restart the inverter; if the fault still exists, contact your installer or Deye service.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 53sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 53
Reverse power flow into the AC grid was detected ('AC reverse irrigation', i.e. reverse feed-in).
CausePower is flowing back into the AC grid beyond what the configuration allows, so the inverter flags reverse feed-in (the manual's remedy column simply restates 'AC reverse irrigation').
Recommended fixIf export to the grid is not intended, check the zero-export/limiter settings and the meter or sensor-clamp installation; restart the inverter and contact your installer if the fault persists.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 53sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 53
Over-current on grid phase U. The manual notes this code has hardly ever appeared in the field.
CauseThe grid current on phase U exceeded the over-current limit.
Recommended fixRestart the inverter; if the code persists after the restart, contact your installer or Deye service and provide the inverter serial number, the installation date and the displayed error code.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 53sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 53
Over-current on grid phase V. The manual notes this code has hardly ever appeared in the field.
CauseThe grid current on phase V exceeded the over-current limit.
Recommended fixRestart the inverter; if the code persists after the restart, contact your installer or Deye service and provide the inverter serial number, the installation date and the displayed error code.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 53sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 53
Over-current on grid phase W. The manual notes this code has hardly ever appeared in the field.
CauseThe grid current on phase W exceeded the over-current limit.
Recommended fixRestart the inverter; if the code persists after the restart, contact your installer or Deye service and provide the inverter serial number, the installation date and the displayed error code.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 53sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 53
Over-current through filter reactor phase A. The manual notes this code has hardly ever appeared in the field.
CauseThe current through filter reactor phase A exceeded the over-current limit.
Recommended fixRestart the inverter; if the code persists after the restart, contact your installer or Deye service and provide the inverter serial number, the installation date and the displayed error code.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 53sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 53
Over-current through filter reactor phase B. The manual notes this code has hardly ever appeared in the field.
CauseThe current through filter reactor phase B exceeded the over-current limit.
Recommended fixRestart the inverter; if the code persists after the restart, contact your installer or Deye service and provide the inverter serial number, the installation date and the displayed error code.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 53sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 53
A DC arc was detected on the PV side.
CauseA DC arc was detected in the PV module cabling (arc-fault protection), usually at a loose or degraded PV cable connection.
Recommended fix1. Check the PV module cable connection and clear the fault. 2. Seek help from Deye if the inverter cannot go back to the normal state.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 53sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 53
The IGBT heat-sink temperature is too high.
CauseThe IGBT heat-sink temperature exceeded the limit - inadequate cooling or high ambient temperature, or a temperature sensor fault, unsuitable firmware, or a wrong model configuration producing a false reading.
Recommended fix1. Check the temperature sensor; check that the firmware is suitable for the hardware and that the inverter is its right model. 2. Restart the inverter; if the fault still exists, contact your installer or Deye service.
Source:sun-7k-g02p1-eu-am2-sun-7-5k-g02p1-eu-am2-sun-8k-g02p1-eu-am2-manual.pdf· page 53sun-9k-g02p1-eu-am2-sun-10k-g02p1-eu-am2-sun-10-5k-g02p1-eu-am2-manual.pdf· page 53
Support for your Deye unit is free for life — our contact page lists our phone and email. If the unit needs replacing, order it online.