What it means
AC main contactor failure — The main AC relay/contactor failed to operate.
Cause: The main AC relay failed to close correctly: a relay fault, a relay driver circuit fault, or software that is not suitable for this inverter (old inverters have no relay detection function).
How to fix it
- Check the relays and the AC voltage of the relays
- Check the relay driver circuit
- Check if the software is not suitable for this inverter (old inverters have no relay detection function)
- Restart the inverter; if the fault still exists, contact your installer or Deye service.