DEYE SUN SG01HP3/SG02HP3 Hybrid Error Codes: Causes & Fixes (69 codes)

This is the complete fault table for the DEYE SUN SG01HP3/SG02HP3 Hybrid Inverter family — 69 codes shared by 17 model numbers, transcribed from the official manual. On DEYE units, a fault code means the unit has cut its output and the red LED stays solid; a warning flashes the red LED while the unit keeps running.

Also coversSUN-5K-SG01HP3-EU-AM2SUN-6K-SG01HP3-EU-AM2SUN-8K-SG01HP3-EU-AM2SUN-10K-SG01HP3-EU-AM2SUN-12K-SG01HP3-EU-AM2SUN-15K-SG01HP3-EU-AM2SUN-20K-SG01HP3-EU-AM2SUN-25K-SG01HP3-EU-AM2SUN-29.9K-SG01HP3-EU-BM3SUN-30K-SG01HP3-EU-BM3SUN-35K-SG01HP3-EU-BM3SUN-40K-SG01HP3-EU-BM4SUN-50K-SG01HP3-EU-BM4SUN-60K-SG02HP3-EU-EM6SUN-70K-SG02HP3-EU-EM6SUN-75K-SG02HP3-EU-EM6SUN-80K-SG02HP3-EU-EM6

Last checked against the official manuals on July 11, 2026.

How to read the severity labels

  • Fault(58)output stops · red LED solid
  • Warning(11)unit keeps running · red LED flashing

Fault codes (58)output stops · red LED solid

F01Fault

PV Input Polarity Reversed.

Fault

DC_Inversed_Failure - the PV DC input is connected with reversed polarity.

CauseThe PV input positive and negative cables are connected in reverse.

Recommended fixCheck the PV input polarity.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 48050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 49062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 49

F02Fault

PV Insulation Failure.

Fault

DC_Insulation_Failure - the insulation of the PV input to ground is abnormal.

CauseThe PV array is not properly grounded, or the impedance of the PV to ground is abnormal.

Recommended fixCheck whether the PV is grounded; then check whether the impedance of the PV to ground is normal.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 48050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 49062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 49

F03Fault

GFDI Failure.

Fault

GFDI_Failure - the ground fault detector/interrupter has detected a fault on the PV side.

CauseThe PV modules are not grounded, or the PV-to-ground impedance is abnormal and leakage current is present.

Recommended fix1. Check whether the PV modules are grounded. 2. Check whether the impedance of the PV to ground is normal and whether there is leakage current.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 48050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 49062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 49

F04Fault

GFDI Ground Failure.

Fault

GFDI_Ground_Failure - grounding fault detected by the ground fault detector/interrupter.

CauseThe PV array is not grounded.

Recommended fixCheck whether the PV is grounded.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 49050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 50062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 50

F05Fault

EEPROM Read Failure.

Fault

EEPROM_Read_Failure - the controller failed to read data from the EEPROM memory.

CauseThe inverter control board could not read its stored settings from the EEPROM memory.

Recommended fixRestart the inverter 3 times and restore the factory settings.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 49050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 50062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 50

F06Fault

EEPROM Write Failure.

Fault

EEPROM_Write_Failure - the controller failed to write data to the EEPROM memory.

CauseThe inverter control board could not write settings to the EEPROM memory.

Recommended fixRestart the inverter 3 times and restore the factory settings.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 49050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 50062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 50

F07Fault

DC/DC Converter 1 Start Failure.

Fault

DCDC1_START_Failure - the BUS voltage cannot be reached by PV or battery.

CauseDC/DC converter 1 failed to start because the internal BUS voltage could not be built up from the PV or battery input.

Recommended fixSwitch off the DC switches and restart the inverter.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 49050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 50062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 50

F08Fault

DC/DC Converter 2 Start Failure.

Fault

DCDC2_START_Failure - the BUS voltage cannot be reached by PV or battery.

CauseDC/DC converter 2 failed to start because the internal BUS voltage could not be built up from the PV or battery input.

Recommended fixSwitch off the DC switches and restart the inverter.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 49050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 50062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 50

F09Fault

IGBT Failure.

Fault

IGBT_Failure - a fault was detected in the IGBT power module.

CauseThe IGBT power module of the inverter reported a fault.

Recommended fixRestart the inverter 3 times and restore the factory settings.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 49050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 50062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 50

F10Fault

Auxiliary Power Board Failure.

Fault

AuxPowerBoard_Failure - the auxiliary power supply board reported a fault.

CauseThe auxiliary power supply board is faulty; this can also be reported when the inverter's power switch is not turned on.

Recommended fix1. First check whether the inverter switch is on. 2. Restart the inverter 3 times and restore the factory settings.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 49050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 50062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 50

F11Fault

AC Main Contactor Failure.

Fault

AC_MainContactor_Failure - the main AC contactor (relay) reported a fault.

CauseThe main AC contactor of the inverter failed its check or did not switch correctly.

Recommended fixRestart the inverter 3 times and restore the factory settings.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 49050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 50062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 50

F12Fault

AC Slave Contactor Failure.

Fault

AC_SlaveContactor_Failure - the slave AC contactor (relay) reported a fault.

CauseThe slave AC contactor of the inverter failed its check or did not switch correctly.

Recommended fixRestart the inverter 3 times and restore the factory settings.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 49050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 50062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 50

F13Fault

Working Mode Change.

Fault

Working_Mode_Change - the inverter's working mode has been changed.

CauseThe grid type or frequency setting has been changed, the battery mode has been changed to 'No battery' mode, or (on some old firmware versions) the system's work mode has been changed.

Recommended fixGenerally this error disappears automatically. if it remains the same, turn off the DC and AC switches for one minute, then turn on the DC and AC switches.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 49050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 50062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 50

F14Fault

DC Overcurrent Failure.

Fault

DC_OverCurr_Failure - overcurrent detected on the DC side.

CauseThe DC-side current exceeded the protection limit.

Recommended fixRestart the inverter 3 times and restore the factory settings.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 49050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 50062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 50

F15Fault

AC Overcurrent (Software).

Fault

AC_OverCurr_SW_Failure - AC side overcurrent fault detected by software.

CauseThe AC-side current exceeded the software protection limit, typically because the backup load power and common load power are beyond the allowed range.

Recommended fix1. Check whether the backup load power and common load power are within the range. 2. Restart and check whether it is normal.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 49050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 50062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 50

F16Fault

GFCI Failure (Leakage Current).

Fault

GFCI_Failure - leakage (residual) current fault.

CauseThe leakage current to ground exceeded the limit, usually due to a PV-side cable ground connection problem.

Recommended fix1. Check the PV side cable ground connection. 2. Restart the system 2-3 times.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 49050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 50062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 50

F17Fault

PV Transient Overcurrent.

Fault

Tz_PV_OverCurr_Fault - transient overcurrent detected on the PV input.

CauseThe PV input current spiked beyond the limit, typically because the PV connection is unstable.

Recommended fix1. Check the PV connection and whether the PV is unstable. 2. Restart the inverter 3 times.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 49050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 50062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 50

F18Fault

AC Transient Overcurrent (Hardware).

Fault

Tz_AC_OverCurr_Fault - AC side overcurrent fault detected by hardware.

CauseThe AC-side current exceeded the hardware protection limit, typically because the backup load power and common load power are beyond the allowed range.

Recommended fix1. Check whether the backup load power and common load power are within the range. 2. Restart and check whether it is normal.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 49050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 50062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 50

F19Fault

Integrated Transient Fault.

Fault

Tz_Integ_Fault - integrated transient hardware protection fault.

CauseAn internal combined (integrated) transient hardware protection was triggered.

Recommended fixRestart the inverter 3 times and restore the factory settings.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 49050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 50062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 50

F20Fault

DC Transient Overcurrent (Hardware).

Fault

Tz_Dc_OverCurr_Fault - DC side overcurrent fault detected by hardware.

CauseThe DC-side current exceeded the hardware protection limit; a PV module or battery connection problem, or starting the inverter under a high power load in off-grid mode, can trigger it.

Recommended fix1. Check the PV module connection and battery connection. 2. In off-grid mode, starting the inverter under a high power load may report F20 - reduce the connected load power. 3. if it remains the same, turn off the DC and AC switches for one minute, then turn on the DC and AC switches.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 50050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 51062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 51

F21Fault

BUS Overcurrent.

Fault

Tz_HV_Overcurr_Fault - overcurrent on the internal high-voltage BUS.

CauseThe DC BUS current exceeded the limit, typically because the PV input current or the battery current setting is too high.

Recommended fix1. Check the PV input current and the battery current setting. 2. Restart the system 2~3 times.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 50050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 51062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 51

F22Fault

Remote Emergency Stop.

Fault

Tz_EmergStop_Fault - the inverter has been shut down remotely.

CauseA remote shutdown command was issued; the inverter is being remotely controlled.

Recommended fixThe inverter is remotely controlled - check the remote control/shutdown source and release the remote stop.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 50050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 51062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 51

F23Fault

Leakage Transient Overcurrent.

Fault

Tz_GFCI_OC_Fault - transient overcurrent of the leakage (residual) current.

CauseThe leakage current spiked beyond the transient limit, usually due to a PV-side cable ground connection problem.

Recommended fix1. Check the PV side cable ground connection. 2. Restart the system 2~3 times.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 50050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 51062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 51

F24Fault

PV Insulation Resistance Too Low.

Fault

DC_Insulation_Fault - the PV isolation resistance is too low.

CauseThe insulation resistance between the PV array and ground is below the limit; the PV panel connections or the inverter's PE grounding may be faulty.

Recommended fix1. Check that the connection of the PV panels and the inverter is firm and correct. 2. Check whether the PE cable of the inverter is connected to ground.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 50050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 51062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 51

F25Fault

DC Feedback Fault.

Fault

DC_Feedback_Fault - abnormal DC feedback detected.

CauseThe inverter detected abnormal DC feedback and tripped its DC feedback protection.

Recommended fixRestart the inverter 3 times and restore the factory settings.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 50050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 51062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 51

F26Fault

BUS Unbalance Fault.

Fault

BusUnbalance_Fault - the internal DC BUS voltages are unbalanced.

CauseThe load power on the 3 phases differs greatly, or there is DC leakage current.

Recommended fix1. Wait for a while and check whether it returns to normal. 2. Restart the system 2~3 times.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 50050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 51062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 51

F27Fault

DC Insulation Fault (Internal).

Fault

DC_Insulation_Fault - internal DC insulation fault.

CauseThe inverter's DC insulation monitoring reported a fault.

Recommended fixRestart the inverter 3 times and restore the factory settings.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 50050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 51062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 51

F28Fault

DC Injection Overcurrent (M1).

Fault

DCIOver_M1_Fault - the DC component of the output current exceeded the limit (measurement channel M1).

CauseThe DC injection (DC component) in the AC output measured on channel M1 exceeded the limit.

Recommended fixRestart the inverter 3 times and restore the factory settings.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 50050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 51062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 51

F29Fault

Parallel Communication Fault.

Fault

Parallel_Comm_Fault - communication fault between paralleled inverters.

CauseThe parallel communication cable connection or the hybrid inverter communication address setting is incorrect; F29 also appears normally during parallel system startup until all inverters are in ON status.

Recommended fix1. When inverters are connected in parallel, check the parallel communication cable connection and the hybrid inverter communication address setting. 2. During the parallel system startup period, inverters will report F29; when all inverters are in ON status, it disappears automatically.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 50050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 51062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 51

F30Fault

AC Main Contactor Fault.

Fault

AC_MainContactor_Fault - the main AC contactor reported a fault.

CauseThe main AC contactor of the inverter failed its check or did not switch correctly.

Recommended fixRestart the inverter 3 times and restore the factory settings.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 50050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 51062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 51

F31Fault

AC Slave Contactor Fault.

Fault

AC_SlaveContactor_Fault - the slave AC contactor reported a fault.

CauseThe slave AC contactor failed its check; an incorrect grid orientation (wiring) can cause it.

Recommended fix1. Check whether the grid orientation is correct. 2. Restart the inverter 3 times and restore the factory settings.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 50050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 51062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 51

F32Fault

DC Injection Overcurrent (M2).

Fault

DCIOver_M2_Fault - the DC component of the output current exceeded the limit (measurement channel M2).

CauseThe DC injection (DC component) in the AC output measured on channel M2 exceeded the limit.

Recommended fixRestart the inverter 3 times and restore the factory settings.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 50050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 51062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 51

F33Fault

AC Overcurrent Fault.

Fault

AC_OverCurr_Fault - overcurrent on the AC (grid) side.

CauseThe grid-side AC current is too large.

Recommended fix1. Check whether the grid current is too large. 2. Restart the inverter 3 times and restore the factory settings.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 50050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 51062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 51

F34Fault

AC Overload Fault.

Fault

AC_Overload_Fault - the backup load exceeds the allowed power.

CauseThe load connected to the backup (Load) port exceeds the allowed power range.

Recommended fixCheck the backup load connection and make sure it is within the allowed power range.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 50050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 51062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 51

F35Fault

No Utility (Grid Lost).

Fault

AC_NoUtility_Fault - no utility grid detected.

CauseThe utility grid is not detected - the grid is down, or the grid voltage/frequency or the grid connection is abnormal.

Recommended fixCheck the grid voltage and frequency and whether the connection of the power grid is normal.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 51050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 52062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 52

F39Fault

Internal AC Overcurrent.

Fault

INT_AC_OverCurr_Fault - inverter internal AC overcurrent.

CauseThe inverter's internal AC current exceeded the limit.

Recommended fixRestart the inverter.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 51050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 52062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 52

F40Fault

Internal DC Overcurrent.

Fault

INT_DC_OverCurr_Fault - inverter internal DC overcurrent.

CauseThe inverter's internal DC current exceeded the limit.

Recommended fixRestart the inverter.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 51050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 52062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 52

F41Fault

Parallel System Stop.

Fault

Parallel_system_Stop - the parallel system has stopped.

CauseAt least one hybrid inverter in the parallel system has shut down; all hybrid inverters in the system then report the F41 fault.

Recommended fixCheck the work status of each hybrid inverter; if at least one hybrid inverter is shut down, restore it so the parallel system can resume.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 51050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 52062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 52

F42Fault

Parallel Version Fault.

Fault

Parallel_Version_Fault - the firmware versions of the paralleled inverters do not match.

CauseThe software/firmware versions of the inverters connected in parallel are not consistent.

Recommended fix1. Check whether the inverter versions are consistent. 2. Contact us to upgrade the software version.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 51050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 52062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 52

F45Fault

Grid Overvoltage.

Fault

AC_UV_OverVolt_Fault - grid voltage out of range (too high).

CauseThe grid voltage is above the range given in the specification.

Recommended fix1. Check that the voltage is in the range of the specification. 2. Check whether the AC cables are firmly and correctly connected.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 51050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 52062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 52

F46Fault

Grid Undervoltage.

Fault

AC_UV_UnderVolt_Fault - grid voltage out of range (too low).

CauseThe grid voltage is below the range given in the specification.

Recommended fix1. Check that the voltage is in the range of the specification. 2. Check whether the AC cables are firmly and correctly connected.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 51050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 52062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 52

F47Fault

Grid Overfrequency.

Fault

AC_OverFreq_Fault - grid frequency out of range (too high).

CauseThe grid frequency is above the range given in the specification.

Recommended fix1. Check whether the frequency is in the range of the specification. 2. Check whether the AC cables are firmly and correctly connected.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 51050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 52062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 52

F48Fault

Grid Underfrequency.

Fault

AC_UnderFreq_Fault - grid frequency out of range (too low).

CauseThe grid frequency is below the range given in the specification.

Recommended fix1. Check whether the frequency is in the range of the specification. 2. Check whether the AC cables are firmly and correctly connected.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 51050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 52062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 52

F49Fault

Grid Current DC Component High (Phase U).

Fault

AC_U_GridCurr_DcHigh_Fault - the DC component of the phase-U grid current is too high.

CauseThe DC component in the grid current of phase U exceeded the limit.

Recommended fixRestart the inverter 3 times and restore the factory settings.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 51050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 52062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 52

F50Fault

Grid Current DC Component High (Phase V).

Fault

AC_V_GridCurr_DcHigh_Fault - the DC component of the phase-V grid current is too high.

CauseThe DC component in the grid current of phase V exceeded the limit.

Recommended fixRestart the inverter 3 times and restore the factory settings.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 51050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 52062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 52

F51Fault

Battery Temperature High.

Fault

Battery_Temp_High_Fault - the battery temperature is too high.

CauseThe battery temperature reported by the BMS is too high.

Recommended fixCheck whether the temperature data of the BMS is too high.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 52050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 53062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 53

F52Fault

BUS Voltage Too High.

Fault

DC_VoltHigh_Fault - the internal DC BUS voltage is too high.

CauseThe BUS voltage is too high because the battery voltage is too high or the PV input voltage exceeds the allowed range.

Recommended fix1. Check whether the battery voltage is too high. 2. Check the PV input voltage and make sure it is within the allowed range.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 52050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 53062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 53

F53Fault

BUS Voltage Too Low.

Fault

DC_VoltLow_Fault - the internal DC BUS voltage is too low.

CauseThe BUS voltage is too low because the battery voltage is too low.

Recommended fix1. Check whether the battery voltage is too low. 2. if the battery voltage is too low, use PV or grid to charge the battery.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 52050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 53062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 53

F54Fault

Battery 2 Voltage High.

Fault

BAT2_VoltHigh_Fault - the terminal voltage of battery input 2 is too high.

CauseThe voltage measured at the battery 2 terminals is above the limit.

Recommended fix1. Check whether the battery 2 terminal voltage is high. 2. Restart the inverter 2 times and restore the factory settings.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 52050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 53062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 53

F55Fault

Battery 1 Voltage High.

Fault

BAT1_VoltHigh_Fault - the terminal voltage of battery input 1 is too high.

CauseThe voltage measured at the battery 1 terminals is above the limit.

Recommended fix1. Check whether the battery 1 terminal voltage is high. 2. Restart the inverter 2 times and restore the factory settings.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 52050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 53062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 53

F56Fault

Battery 1 Voltage Low.

Fault

BAT1_VoltLow_Fault - the terminal voltage of battery input 1 is too low.

CauseThe voltage measured at the battery 1 terminals is below the limit.

Recommended fix1. Check whether the battery 1 terminal voltage is low. 2. Restart the inverter 2 times and restore the factory settings.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 52050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 53062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 53

F57Fault

Battery 2 Voltage Low.

Fault

BAT2_VoltLow_Fault - the terminal voltage of battery input 2 is too low.

CauseThe voltage measured at the battery 2 terminals is below the limit.

Recommended fix1. Check whether the battery 2 terminal voltage is low. 2. Restart the inverter 2 times and restore the factory settings.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 52050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 53062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 53

F58Fault

Battery Communication Lost.

Fault

Battery_Comm_Lose - communication with the battery BMS has been lost.

CauseThe communication between the hybrid inverter and the battery BMS is disconnected while the 'BMS_Err-Stop' function is active.

Recommended fixTo avoid this error, disable the 'BMS_Err-Stop' item on the LCD.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 52050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 53062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 53

F60Fault

Generator Fault.

Fault

GEN_FAULT - the generator input is abnormal.

CauseThe voltage or frequency of the generator is abnormal.

Recommended fixCheck whether the voltage and frequency of the generator are normal, and then restart.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 52050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 53062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 53

F61Fault

Inverter Manually Off.

Fault

INVERTER_Manual_OFF - the inverter has been switched off manually.

CauseThe inverter's power switch is turned off (manual shutdown).

Recommended fixCheck whether the switch of the inverter is turned on, restart the inverter, and restore the factory settings.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 52050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 53062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 53

F62Fault

DRMs Stop.

Fault

DRMs_Stop - the inverter has been stopped by a demand response (DRM) command.

CauseA Demand Response Mode (DRM) command is active and has stopped the inverter.

Recommended fixCheck whether the DRM function is active.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 52050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 53062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 53

F63Fault

Arc Fault.

Fault

ARC_Fault - a PV DC arc fault was detected.

CauseAn electric arc was detected on the PV module cabling (ARC fault detection is only for the US market).

Recommended fixCheck the PV module cable connection and clear the fault.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 52050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 53062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 53

F64Fault

Heat Sink Overtemperature.

Fault

Heatsink_HighTemp_Fault - the heat sink temperature is too high.

CauseThe heat sink temperature exceeded the limit; the working environment temperature may be too high.

Recommended fix1. Check whether the working environment temperature is too high. 2. Turn off the inverter for 10 minutes and restart.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 52050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 53062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 53

Warning codes (11)unit keeps running · red LED flashing

W02Warning

Internal Fan Warning.

Warning

FAN_IN_Warn - the inverter's internal fan is operating abnormally.

CauseThe internal fan is running abnormally, or its cable connection inside the inverter is loose or faulty.

Recommended fix1. Check the operating status of the fan. 2. if the fan is running abnormally, open the cover of the inverter and check the connection of the fan.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 48050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 49062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 49

W03Warning

Grid Phase Warning.

Warning

Grid_phase_warn - the phase sequence detected at the grid connection is abnormal.

CauseThe phase sequence connection of the power grid is incorrect, or the configured grid type does not match the actual grid.

Recommended fix1. Check the phase sequence connection of the power grid. 2. Try to change the grid type (e.g. 240/120). 3. if there is still no solution, check the wiring at the grid end.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 48050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 49062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 49

W04Warning

Meter Offline Warning.

Warning

Meter_offline_warn - meter communication failure.

CauseCommunication between the inverter and the external energy meter has been lost, or the meter wiring is abnormal.

Recommended fixCheck whether the meter has successful communication and whether the wiring is normal.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 48050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 49062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 49

W05Warning

CT Wrong Direction Warning.

Warning

CT_WRONG_direction_warn - a current transformer (CT) is installed in the wrong direction or location.

CauseThe arrow on the CT case does not point toward the inverter, or the CTs are installed in the wrong location.

Recommended fixCheck whether the arrow on the CT case points to the inverter, and check that the installation locations of the CTs are correct.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 48050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 49062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 49

W06Warning

CT Not Connected Warning.

Warning

CT_Notconnect_warn - a current transformer (CT) is not detected by the inverter.

CauseThe CT wires are not connected correctly or are disconnected.

Recommended fixCheck whether the wires of the CTs are connected correctly.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 48050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 49062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 49

W07Warning

External Fan 1 Warning.

Warning

FAN_OUT1_Warn - external fan 1 is operating abnormally.

CauseExternal fan 1 is not connected correctly or is not operating normally.

Recommended fixCheck whether the fan is connected correctly and operating normally.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 48050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 49062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 49

W08Warning

External Fan 2 Warning.

Warning

FAN_OUT2_Warn - external fan 2 is operating abnormally.

CauseExternal fan 2 is not connected correctly or is not operating normally.

Recommended fixCheck whether the fan is connected correctly and operating normally.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 48050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 49062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 49

W09Warning

External Fan 3 Warning.

Warning

FAN_OUT3_Warn - external fan 3 is operating abnormally.

CauseExternal fan 3 is not connected correctly or is not operating normally.

Recommended fixCheck whether the fan is connected correctly and operating normally.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 48050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 49062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 49

W10Warning

Volt-Watt Response Activated.

Warning

VW_activate - the volt-watt (V-W) power response has been activated by high grid-port voltage.

CauseThe grid port voltage has risen high enough to trigger the volt-watt derating response; this can be caused by high grid voltage or by an AC cable that is too thin to carry the current.

Recommended fix1. Measure whether the grid port voltage is too high. 2. Check whether the AC cable is too thin to carry the current.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 48050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 49062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 49

W31Warning

Battery Communication Warning.

Warning

Battery_comm_warn - abnormal communication between the inverter and the battery.

CauseThe BMS connection is unstable, or the BMS data is abnormal.

Recommended fix1. Check whether the BMS connection is stable. 2. Check whether the BMS data is abnormal.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 48050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 49062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 49

W32Warning

Parallel Communication Warning.

Warning

Parallel_comm_warn - unstable communication between paralleled inverters.

CauseThe parallel communication line connection is unstable (for example, wound together with other cables), or the parallel DIP switch is not on.

Recommended fix1. Check the connection of the parallel communication line; do not wind the parallel communication line together with other cables. 2. Check whether the parallel DIP switch is on.

Source:037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf· page 48050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf· page 49062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf· page 49

Still seeing a code on your SUN SG01HP3/SG02HP3 Hybrid?

Send us the code on your screen and a DEYE technician will reply with the exact steps for your unit. Support is free for life — a first diagnosis never needs a callout.

Keep troubleshooting

Related devices

Common questions about SUN SG01HP3/SG02HP3 Hybrid error codes

What is the difference between a fault and a warning on the SUN SG01HP3/SG02HP3 Hybrid?
A fault cuts the unit's output and the red LED stays solid — this page lists 58 of them for the SUN SG01HP3/SG02HP3 Hybrid. A warning only flashes the red LED and the unit keeps running; there are 11 warning codes here. Resolve the cause of a fault before restarting; warnings can usually be cleared while the unit runs.
Which model numbers does this page cover?
The SUN SG01HP3/SG02HP3 Hybrid shares its firmware and fault table with 16 other model numbers: SUN-5K-SG01HP3-EU-AM2, SUN-6K-SG01HP3-EU-AM2, SUN-8K-SG01HP3-EU-AM2, SUN-10K-SG01HP3-EU-AM2, SUN-12K-SG01HP3-EU-AM2, SUN-15K-SG01HP3-EU-AM2, SUN-20K-SG01HP3-EU-AM2, SUN-25K-SG01HP3-EU-AM2, SUN-29.9K-SG01HP3-EU-BM3, SUN-30K-SG01HP3-EU-BM3, SUN-35K-SG01HP3-EU-BM3, SUN-40K-SG01HP3-EU-BM4, SUN-50K-SG01HP3-EU-BM4, SUN-60K-SG02HP3-EU-EM6, SUN-70K-SG02HP3-EU-EM6, SUN-75K-SG02HP3-EU-EM6, SUN-80K-SG02HP3-EU-EM6. If your unit is any of these, every code on this page applies to it.
Where do these codes come from?
Every entry was transcribed from 037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf, 050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf, 062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf — DEYE's official documentation. Each row cites its source manual (and page where printed), so you can verify the wording before acting on it.

Compiled from official DEYE user manuals. Always consult your device manual and a qualified technician before performing repairs.