What it means
AC Line W,U over voltage — The W-U line voltage is above the protection setting.
Cause: The line voltage between phases W and U exceeds the protection setting; an AC cable that is too thin raises the voltage at the inverter terminals under feed-in.
How to fix it
- 1Check the AC voltage protection setting, and check if the AC cable is too thin.
- 2Check the voltage difference between the LCD and a meter.
Source: 041_BManual_SUN-120_125_130_135_136K-G01P3-EU-BM8_20251021_en_a2166559.pdf, p.63 · 065_BManual_SUN-7_7.5_8K-G02P1-EU-AM2_20260625_en_4466f08b.pdf, p.52 · 032_BManual_SUN-9_10_10.5K-G02P1-EU-AM2_20260625_en_df0f2106.pdf, p.52 · +4 more official manuals
Also applies to:SUN-6K-G06-LV-P1SUN-8K-G06-LV-P1SUN-6K-G06P3-EU-BM2-LV-P1SUN-8K-G06P3-EU-BM2-LV-P1SUN-10K-G05-LVSUN-12K-G05-LVSUN-15K-G05-LVSUN-15K-G06P3-EU-BM2-P1+71
What it means
AC Line W,U over voltage — The line voltage between phases W and U is above the protection setting.
Cause: Grid W-U line voltage above the protection setting, or an AC cable that is too thin causing extra voltage rise at the inverter terminals.
How to fix it
Check the AC voltage protection setting; check if the AC cable is too thin; check the voltage difference between the LCD and a meter.
Source: 063_BManual_SUN-6K-G06-LV-P1_20250923_en_30a96699.pdf, p.58 · 031_BManual_SUN-1_1.5_2_2.2_2.5_2.7_3_3.3_3.6_4K-G04P1-EU-AM1_20260624_en_15adc00c.pdf, p.54 · 036_BManual_SUN-3_4_5_6_7_8_9_10_12_15K-G06P3-EU-BM2_20250506_en_0eb78440.pdf, p.58
Also applies to:SUN-3.6K-SG05LP1-EU-SM2-PSUN-5K-SG05LP1-EU-SM2-PSUN-6K-SG05LP1-EU-SM2-PSUN-7K-SG05LP1-EU-SM2-PSUN-7.6K-SG05LP1-EU-SM2-PSUN-8K-SG05LP1-EU-SM2-PSUN-10K-SG05LP1-EU-SM2-PSUN-7.6K-SG01LP1-EU+21
What it means
Parallel system stop — The parallel system has stopped.
Cause: One hybrid inverter in the parallel system is in OFF status, so the other hybrid inverters report F41.
How to fix it
- 1Check the hybrid inverter working status: if one inverter is in OFF status, the other inverters may report F41 in the parallel system.
- 2If the fault still exists, contact Deye for help.
Source: 039_BManual_SUN-3.6_5_6_7_7.6_8_10K-SG05LP1-EU-SM2-P_20260428_en_70c401a6.pdf, p.50 · 043_BManual_SUN-12_14_16K-SG01LP1-EU_20260519_en_703e15ac.pdf, p.46 · 052_BManual_SUN-_3.6-6_K-OG01LP1-EU-AM2_20260406_en_dc31b173.pdf, p.46 · +4 more official manuals
Also applies to:SUN-5K-SG01HP3-EU-AM2SUN-6K-SG01HP3-EU-AM2SUN-8K-SG01HP3-EU-AM2SUN-10K-SG01HP3-EU-AM2SUN-12K-SG01HP3-EU-AM2SUN-15K-SG01HP3-EU-AM2SUN-20K-SG01HP3-EU-AM2SUN-25K-SG01HP3-EU-AM2+9
What it means
Parallel System Stop — Parallel_system_Stop - the parallel system has stopped.
Cause: At least one hybrid inverter in the parallel system has shut down; all hybrid inverters in the system then report the F41 fault.
How to fix it
Check the work status of each hybrid inverter; if at least one hybrid inverter is shut down, restore it so the parallel system can resume.
Source: 037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf, p.51 · 050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf, p.52 · 062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf, p.52
Also applies to:SUN-5K-SG02LP2-US-AM2SUN-6K-SG02LP2-US-AM2SUN-7.6K-SG02LP2-US-AM2SUN-8K-SG02LP2-US-AM2SUN-10K-SG02LP2-US-AM3SUN-12K-SG02LP2-US-AM3
What it means
Parallel System Stop — Parallel system stop - the parallel system has stopped.
Cause: One hybrid inverter in the parallel system is in OFF status, so the other hybrid inverters in the parallel system report the F41 fault.
How to fix it
- 1Check the hybrid inverter working status
- 2If the fault still exists, contact us for help.
Source: 059_BManual_SUN-5_6_7.6_8_10_12K-SG02LP2-US-AM2_AM3_20260406_en_fb6a30c7.pdf, p.55
Also applies to:SUN-5K-SG04LP3-EUSUN-6K-SG04LP3-EUSUN-8K-SG04LP3-EUSUN-10K-SG04LP3-EUSUN-12K-SG04LP3-EUSUN-3K-SG05LP3-EU-SM2SUN-4K-SG05LP3-EU-SM2SUN-5K-SG05LP3-EU-SM2+9
What it means
Parallel System Stop — Parallel system stop - the parallel system has stopped.
Cause: One hybrid inverter in the parallel system has shut down; all hybrid inverters then report the F41 fault.
How to fix it
- 1Check the hybrid inverter work status
- 2If the fault still exists, contact us for help.
Source: 038_BManual_SUN-5_6_8_10_12K-SG04LP3-EU_20260319_en_081932c1.pdf, p.47 · 040_BManual_SUN-3_4_5_6_8_10_12K-SG05LP3-EU-SM2_20260319_en_b0183b7d.pdf, p.47 · 044_BManual_SUN-14_15_16_18_20K-SG05LP3-EU-SM2_20260319_en_ac7cdbd1.pdf, p.47
Energy storage systemFault Also applies to:AI-W5.1-5P3-EU-B-ESSAI-W5.1-6P3-EU-B-ESSAI-W5.1-8P3-EU-B-ESSAI-W5.1-10P3-EU-B-ESSAI-W5.1-12P3-EU-B-ESS
What it means
Parallel system stop
Cause: One inverter in the parallel system shut down, so all paralleled hybrid inverters report F41.
How to fix it
- 1Check the work status of every hybrid inverter in the parallel system and restore the one that shut down.
- 2If the fault still exists, contact Deye for help.
Source: 002_Download_4e90fe7a.pdf, p.47
Energy storage systemFault Also applies to:GB-SL5K-EUGB-SL6K-EUGB-SL8K-EUGB-SL10K-EUGB-SL12K-EUGB-SL15K-EUGB-SL20K-EUGB-SL Pro 5K-EU+6
What it means
Parallel_system_Stop — Parallel system stop.
Cause: One inverter in the parallel system shut down, so all paralleled hybrid inverters report F41.
How to fix it
- 1Check the work status of every hybrid inverter in the parallel system and restore the one that shut down.
- 2If the fault still exists, contact Deye for help.
Source: 081_deye_gb_sl_pro_user_manual_46fa941a.pdf, p.50 · 010_Download_cc05df18.pdf, p.45
Also applies to:GB-A
What it means
ALARM_ID_POS_RELAY_DRIVE_FAULT — Total positive relay drive failure.
Cause: The drive circuit for the main positive relay failed - the relay coil or its driver cannot actuate the relay.
How to fix it
- 1Restart the system.
- 2If the fault persists, the relay drive circuit needs service - contact Deye support.
Source: 008_deye_ess_user_manual_gb_a_jpnen_v02_20250829_3fea617e.pdf, p.14