56Fault

DEYE inverter error 56 (F56)

DC busbar voltage is too low

Also displayed as F56 on some models.

Faultthe inverter cuts its output and the red LED stays solid until the fault is cleared.

The exact meaning depends on your model:

Also applies to:SUN-120K-G01P3-EU-BM8SUN-125K-G01P3-EU-BM8SUN-130K-G01P3-EU-BM8SUN-135K-G01P3-EU-BM8SUN-136K-G01P3-EU-BM8SUN-7K-G02P1-EU-AM2SUN-7.5K-G02P1-EU-AM2SUN-8K-G02P1-EU-AM2+3

What it means

DC busbar voltage is too lowThe DC bus voltage is below the limit.

Cause: The PV input voltage is low - it always happens in the early morning; if F56 appears while the inverter is running, a loss of the driver or firmware that needs updating may be responsible.

How to fix it

  1. Check the PV voltage and the Ubus voltage - in the early morning this normally just reflects low PV input voltage
  2. If it shows while the inverter is running, the driver may have been lost or the firmware may need updating
  3. Restart the inverter; if the fault still exists, contact your installer or Deye service.

Source: 041_BManual_SUN-120_125_130_135_136K-G01P3-EU-BM8_20251021_en_a2166559.pdf, p.63 · 065_BManual_SUN-7_7.5_8K-G02P1-EU-AM2_20260625_en_4466f08b.pdf, p.53 · 032_BManual_SUN-9_10_10.5K-G02P1-EU-AM2_20260625_en_df0f2106.pdf, p.53

Also applies to:SUN-60K-G03SUN-70K-G03SUN-75K-G03SUN-80K-G03SUN-90K-G03SUN-100K-G03SUN-110K-G03SUN-60K-G01P3-EU-AM8-LV+7

What it means

DC busbar voltage is too lowThe DC bus voltage is below the limit.

Cause: The PV input voltage is low - it always happens in the early morning; if F56 appears while the inverter is running, a loss of the driver or firmware that needs updating may be responsible.

How to fix it

  1. Check the PV voltage and the Ubus voltage - in the early morning this normally just reflects low PV input voltage
  2. If it shows while the inverter is running, the driver may have been lost or the firmware may need updating
  3. Restart the inverter; if the fault still exists, contact your installer.

Source: 033_BManual_SUN-70_75_80_90_100_110K-G03_20260702_en_a9db1e1b.pdf, p.63 · 042_BManual_SUN-120_125_130_135_136K-G01P3-EU-AM8_20260702_en_05f936e3.pdf, p.62 · 060_BManual_SUN-60_70_75K-G01P3-EU-AM8-LV_20260701_en_f559aeec.pdf, p.62 · +1 more official manuals

Also applies to:SUN-6K-G06-LV-P1SUN-8K-G06-LV-P1SUN-6K-G06P3-EU-BM2-LV-P1SUN-8K-G06P3-EU-BM2-LV-P1SUN-10K-G05-LVSUN-12K-G05-LVSUN-15K-G05-LVSUN-15K-G06P3-EU-BM2-P1+71

What it means

DC busbar voltage is too lowThe DC bus voltage is below its lower limit.

Cause: The PV input voltage is low - it always happens in the early morning; if F56 appears while the inverter is running, it may be loss of a driver or firmware that needs an update.

How to fix it

  1. Check the PV voltage and Ubus voltage; update the firmware if needed.
  2. Restart the inverter; if the fault still exists, contact your installer or Deye service.

Source: 063_BManual_SUN-6K-G06-LV-P1_20250923_en_30a96699.pdf, p.59 · 031_BManual_SUN-1_1.5_2_2.2_2.5_2.7_3_3.3_3.6_4K-G04P1-EU-AM1_20260624_en_15adc00c.pdf, p.55 · 036_BManual_SUN-3_4_5_6_7_8_9_10_12_15K-G06P3-EU-BM2_20250506_en_0eb78440.pdf, p.59

Also applies to:SUN-3.6K-SG05LP1-EU-SM2-PSUN-5K-SG05LP1-EU-SM2-PSUN-6K-SG05LP1-EU-SM2-PSUN-7K-SG05LP1-EU-SM2-PSUN-7.6K-SG05LP1-EU-SM2-PSUN-8K-SG05LP1-EU-SM2-PSUN-10K-SG05LP1-EU-SM2-PSUN-7.6K-SG01LP1-EU+21

What it means

DC busbar voltage is too lowBattery voltage low: the DC busbar voltage is too low.

Cause: The battery voltage is too low.

How to fix it

  1. Check whether the battery voltage is too low; if it is, use PV or grid power to charge the battery.
  2. Seek help from Deye if the inverter cannot go back to the normal state.

Source: 039_BManual_SUN-3.6_5_6_7_7.6_8_10K-SG05LP1-EU-SM2-P_20260428_en_70c401a6.pdf, p.50 · 043_BManual_SUN-12_14_16K-SG01LP1-EU_20260519_en_703e15ac.pdf, p.46 · 052_BManual_SUN-_3.6-6_K-OG01LP1-EU-AM2_20260406_en_dc31b173.pdf, p.46 · +4 more official manuals

Also applies to:SUN-5K-SG01HP3-EU-AM2SUN-6K-SG01HP3-EU-AM2SUN-8K-SG01HP3-EU-AM2SUN-10K-SG01HP3-EU-AM2SUN-12K-SG01HP3-EU-AM2SUN-15K-SG01HP3-EU-AM2SUN-20K-SG01HP3-EU-AM2SUN-25K-SG01HP3-EU-AM2+9

What it means

Battery 1 Voltage LowBAT1_VoltLow_Fault - the terminal voltage of battery input 1 is too low.

Cause: The voltage measured at the battery 1 terminals is below the limit.

How to fix it

  1. Check whether the battery 1 terminal voltage is low
  2. Restart the inverter 2 times and restore the factory settings.

Source: 037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf, p.52 · 050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf, p.53 · 062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf, p.53

Also applies to:SUN-5K-SG02LP2-US-AM2SUN-6K-SG02LP2-US-AM2SUN-7.6K-SG02LP2-US-AM2SUN-8K-SG02LP2-US-AM2SUN-10K-SG02LP2-US-AM3SUN-12K-SG02LP2-US-AM3SUN-5K-SG04LP3-EUSUN-6K-SG04LP3-EU+15

What it means

DC Busbar Voltage Too LowDC busbar voltage is too low - battery voltage low.

Cause: The DC busbar voltage is too low because the battery voltage is too low.

How to fix it

  1. Check whether the battery voltage is too low
  2. If the battery voltage is too low, use PV or grid to charge the battery
  3. Seek help from us if it cannot go back to the normal state.

Source: 059_BManual_SUN-5_6_7.6_8_10_12K-SG02LP2-US-AM2_AM3_20260406_en_fb6a30c7.pdf, p.55 · 038_BManual_SUN-5_6_8_10_12K-SG04LP3-EU_20260319_en_081932c1.pdf, p.48 · 040_BManual_SUN-3_4_5_6_8_10_12K-SG05LP3-EU-SM2_20260319_en_b0183b7d.pdf, p.48 · +1 more official manuals

AI-W5.1 ESS

Energy storage systemFault

Also applies to:AI-W5.1-5P3-EU-B-ESSAI-W5.1-6P3-EU-B-ESSAI-W5.1-8P3-EU-B-ESSAI-W5.1-10P3-EU-B-ESSAI-W5.1-12P3-EU-B-ESS

What it means

DC busbar voltage is too lowBUS voltage is too low (battery voltage low).

Cause: The internal BUS voltage is below its limit - typically the battery voltage is too low.

How to fix it

  1. Check whether the battery voltage is too low; if so, use PV or grid to charge the battery.
  2. Seek help from Deye if it does not recover.

Source: 002_Download_4e90fe7a.pdf, p.48

GB-SL / GB-SL Pro ESS

Energy storage systemFault

Also applies to:GB-SL5K-EUGB-SL6K-EUGB-SL8K-EUGB-SL10K-EUGB-SL12K-EUGB-SL15K-EUGB-SL20K-EUGB-SL Pro 5K-EU+6

What it means

BAT1_VoltLow_FaultBattery 1 terminal voltage is too low.

Cause: The voltage measured at the battery 1 terminals is below the limit - the battery is over-discharged or the settings are wrong.

How to fix it

  1. Check the battery 1 terminal voltage, restart the inverter twice and restore the factory settings.
  2. Seek help from Deye if it does not recover.

Source: 081_deye_gb_sl_pro_user_manual_46fa941a.pdf, p.51 · 010_Download_cc05df18.pdf, p.46

Frequently asked questions

What does error 56 mean on a DEYE inverter?
It depends on the model — 12 devices use code 56. On the SUN G01P3-EU-BM8 Series it means: DC busbar voltage is too low. The card for each model on this page gives its exact meaning and fix.
Is error 56 a fault or a warning?
56 is a fault code: the inverter cuts its output and the red LED stays solid until it is cleared.
How do I clear or fix error 56?
1. Check the PV voltage and the Ubus voltage - in the early morning this normally just reflects low PV input voltage. The exact steps for each affected model are listed on this page.

Related error codes

Prefer the full written guide? Read the complete DEYE inverter error-code guide

Compiled from official DEYE user manuals. Always consult your device manual and a qualified technician before performing repairs.