DEYE inverter error 58 (F58)

AC grid U over current

Also displayed as F58 on some models.

Faultthe inverter cuts its output and the red LED stays solid until the fault is cleared.

The exact meaning depends on your model:

Also applies to:SUN-120K-G01P3-EU-BM8SUN-125K-G01P3-EU-BM8SUN-130K-G01P3-EU-BM8SUN-135K-G01P3-EU-BM8SUN-136K-G01P3-EU-BM8SUN-7K-G02P1-EU-AM2SUN-7.5K-G02P1-EU-AM2SUN-8K-G02P1-EU-AM2+3

What it means

AC grid U over currentOver-current on grid phase U. The manual notes this code has hardly ever appeared in the field.

Cause: The grid current on phase U exceeded the over-current limit.

How to fix it

Restart the inverter; if the code persists after the restart, contact your installer or Deye service and provide the inverter serial number, the installation date and the displayed error code.

Source: 041_BManual_SUN-120_125_130_135_136K-G01P3-EU-BM8_20251021_en_a2166559.pdf, p.63 · 065_BManual_SUN-7_7.5_8K-G02P1-EU-AM2_20260625_en_4466f08b.pdf, p.53 · 032_BManual_SUN-9_10_10.5K-G02P1-EU-AM2_20260625_en_df0f2106.pdf, p.53

Also applies to:SUN-60K-G03SUN-70K-G03SUN-75K-G03SUN-80K-G03SUN-90K-G03SUN-100K-G03SUN-110K-G03SUN-60K-G01P3-EU-AM8-LV+7

What it means

AC grid U over currentOver-current on grid phase U.

Cause: The grid current on phase U exceeded the over-current limit.

How to fix it

Restart the inverter; if the fault is not ruled out, contact the installer or the manufacturer's customer service.

Source: 033_BManual_SUN-70_75_80_90_100_110K-G03_20260702_en_a9db1e1b.pdf, p.63 · 042_BManual_SUN-120_125_130_135_136K-G01P3-EU-AM8_20260702_en_05f936e3.pdf, p.62 · 060_BManual_SUN-60_70_75K-G01P3-EU-AM8-LV_20260701_en_f559aeec.pdf, p.62 · +1 more official manuals

Also applies to:SUN-6K-G06-LV-P1SUN-8K-G06-LV-P1SUN-6K-G06P3-EU-BM2-LV-P1SUN-8K-G06P3-EU-BM2-LV-P1SUN-10K-G05-LVSUN-12K-G05-LVSUN-15K-G05-LVSUN-15K-G06P3-EU-BM2-P1+27

What it means

AC grid U over currentOver-current on the U-phase grid current.

Cause: The U-phase grid current exceeded its protection limit.

How to fix it

Restart the inverter; if the fault is not ruled out, contact the installer or manufacturer customer service.

Source: 063_BManual_SUN-6K-G06-LV-P1_20250923_en_30a96699.pdf, p.59

Also applies to:SUN-1K-G04P1-EU-AM1SUN-1.5K-G04P1-EU-AM1SUN-2K-G04P1-EU-AM1SUN-2.2K-G04P1-EU-AM1SUN-2.5K-G04P1-EU-AM1SUN-2.7K-G04P1-EU-AM1SUN-3K-G04P1-EU-AM1SUN-3.3K-G04P1-EU-AM1+36

What it means

AC grid U over currentOver-current on the U-phase grid current.

Cause: The U-phase grid current exceeded its protection limit.

How to fix it

Deye states this code has hardly ever appeared in the field; contact your installer or Deye service if it occurs.

Source: 031_BManual_SUN-1_1.5_2_2.2_2.5_2.7_3_3.3_3.6_4K-G04P1-EU-AM1_20260624_en_15adc00c.pdf, p.55 · 036_BManual_SUN-3_4_5_6_7_8_9_10_12_15K-G06P3-EU-BM2_20250506_en_0eb78440.pdf, p.59

Also applies to:SUN-3.6K-SG05LP1-EU-SM2-PSUN-5K-SG05LP1-EU-SM2-PSUN-6K-SG05LP1-EU-SM2-PSUN-7K-SG05LP1-EU-SM2-PSUN-7.6K-SG05LP1-EU-SM2-PSUN-8K-SG05LP1-EU-SM2-PSUN-10K-SG05LP1-EU-SM2-PSUN-7.6K-SG01LP1-EU+21

What it means

BMS communication faultCommunication between the hybrid inverter and the battery BMS is disconnected while 'BMS_Err-Stop' is active.

Cause: The communication link between the hybrid inverter and the battery BMS has been lost while the 'BMS_Err-Stop' setting is enabled.

How to fix it

  1. Restore the communication between the inverter and the battery BMS.
  2. If you do not want this fault reported, you can disable the 'BMS_Err-Stop' item on the LCD.
  3. If the fault still exists, contact Deye for help.

Source: 039_BManual_SUN-3.6_5_6_7_7.6_8_10K-SG05LP1-EU-SM2-P_20260428_en_70c401a6.pdf, p.51 · 043_BManual_SUN-12_14_16K-SG01LP1-EU_20260519_en_703e15ac.pdf, p.47 · 052_BManual_SUN-_3.6-6_K-OG01LP1-EU-AM2_20260406_en_dc31b173.pdf, p.46 · +4 more official manuals

Also applies to:SUN-5K-SG01HP3-EU-AM2SUN-6K-SG01HP3-EU-AM2SUN-8K-SG01HP3-EU-AM2SUN-10K-SG01HP3-EU-AM2SUN-12K-SG01HP3-EU-AM2SUN-15K-SG01HP3-EU-AM2SUN-20K-SG01HP3-EU-AM2SUN-25K-SG01HP3-EU-AM2+9

What it means

Battery Communication LostBattery_Comm_Lose - communication with the battery BMS has been lost.

Cause: The communication between the hybrid inverter and the battery BMS is disconnected while the 'BMS_Err-Stop' function is active.

How to fix it

To avoid this error, disable the 'BMS_Err-Stop' item on the LCD.

Source: 037_BManual_SUN-5_6_8_10_12_15_20_25K-SG01HP3-EU-AM2_20260224_en_9ef2717c.pdf, p.52 · 050_BManual_SUN-29.9_30_35_40_50K-SG01HP3-EU-BM3_4_20260224_en_544e1b2f.pdf, p.53 · 062_BManual__SUN-60_70_75_80K-SG02HP3-EU-EM6_20260224_en_38cbc9f6.pdf, p.53

Also applies to:SUN-5K-SG02LP2-US-AM2SUN-6K-SG02LP2-US-AM2SUN-7.6K-SG02LP2-US-AM2SUN-8K-SG02LP2-US-AM2SUN-10K-SG02LP2-US-AM3SUN-12K-SG02LP2-US-AM3SUN-5K-SG04LP3-EUSUN-6K-SG04LP3-EU+15

What it means

BMS Communication FaultBMS communication fault - communication with the battery BMS has been lost.

Cause: The communication between the hybrid inverter and the battery BMS is disconnected while the 'BMS_Err-Stop' function is active.

How to fix it

  1. If you do not want this to happen, disable the 'BMS_Err-Stop' item on the LCD
  2. If the fault still exists, contact us for help.

Source: 059_BManual_SUN-5_6_7.6_8_10_12K-SG02LP2-US-AM2_AM3_20260406_en_fb6a30c7.pdf, p.55 · 038_BManual_SUN-5_6_8_10_12K-SG04LP3-EU_20260319_en_081932c1.pdf, p.48 · 040_BManual_SUN-3_4_5_6_8_10_12K-SG05LP3-EU-SM2_20260319_en_b0183b7d.pdf, p.48 · +1 more official manuals

AI-W5.1 ESS

Energy storage systemFault

Also applies to:AI-W5.1-5P3-EU-B-ESSAI-W5.1-6P3-EU-B-ESSAI-W5.1-8P3-EU-B-ESSAI-W5.1-10P3-EU-B-ESSAI-W5.1-12P3-EU-B-ESS

What it means

BMS communication faultBattery BMS communication lost.

Cause: Communication between the hybrid inverter and the battery BMS disconnected while 'BMS_Err-Stop' is active.

How to fix it

  1. Restore the BMS communication link (cable, pinout, protocol).
  2. If you do not want the inverter to stop on BMS loss, disable the 'BMS_Err-Stop' item on the LCD.
  3. If the fault still exists, contact Deye for help.

Source: 002_Download_4e90fe7a.pdf, p.48

GB-SL / GB-SL Pro ESS

Energy storage systemFault

Also applies to:GB-SL5K-EUGB-SL6K-EUGB-SL8K-EUGB-SL10K-EUGB-SL12K-EUGB-SL15K-EUGB-SL20K-EUGB-SL Pro 5K-EU+6

What it means

Battery_comm_LoseBattery BMS communication lost.

Cause: Communication between the hybrid inverter and the battery BMS disconnected while 'BMS_Err-Stop' is active.

How to fix it

  1. Restore the BMS communication link (cable, pinout, protocol).
  2. If you do not want the inverter to stop on BMS loss, disable the 'BMS_Err-Stop' item on the LCD.
  3. If the fault still exists, contact Deye for help.

Source: 081_deye_gb_sl_pro_user_manual_46fa941a.pdf, p.51 · 010_Download_cc05df18.pdf, p.46

Frequently asked questions

What does error 58 mean on a DEYE inverter?
It depends on the model — 12 devices use code 58. On the SUN G01P3-EU-BM8 Series it means: AC grid U over current. The card for each model on this page gives its exact meaning and fix.
Is error 58 a fault or a warning?
58 is a fault code: the inverter cuts its output and the red LED stays solid until it is cleared.
How do I clear or fix error 58?
Restart the inverter; if the code persists after the restart, contact your installer or Deye service and provide the inverter serial number, the installation date and the displayed error code. The exact steps for each affected model are listed on this page.

Related error codes

Prefer the full written guide? Read the complete DEYE inverter error-code guide

Compiled from official DEYE user manuals. Always consult your device manual and a qualified technician before performing repairs.